360 dvs series direct vent fireplaces, Hearth final finishing, Framing & finishing – Majestic Appliances 360DVS3 User Manual

Page 10: Gas specifications gas inlet & manifold pressures, Gas line installation

Advertising
background image

10

360 DVS Series Direct Vent Fireplaces

10006326

A hearth is not mandatory; however, for aesthetic
purposes, we recommend installing a noncombustible
hearth that projects out 12” (305mm) or more from the
front of the fireplace.
Cold climate installation recommendation:

When installing this unit against a noninsu-
lated exterior wall or chase, it is mandatory
the outer walls be insulated to conform to
applicable insulation codes.

Hearth

Final Finishing

1. Choose the unit location.
2. Place the unit into position and secure it to the floor

with 1¹⁄₂” (38mm) screws or nails. Holes to secure
the unit to the floor are located behind the access
door grille on the left and right sides of the unit.

3. Frame in the fireplace with a header across the top.

It is important to allow for the finished wall face when
setting the depth of the frame.

4. Drywall (sheetrock) or wood material may be placed

with a zero clearance to the top edges of the appli-
ance when finishing walls above sides of the appli-
ance with glass windows. NOTE: Attach wall finish-
ing to constructed frame, not the appliance.

5. On 360DVSL and 360DVSR, drywall, wood, or wood

molding may be placed with zero clearance to the
rear wall of the unit, along the vertical edge formed
by the standoffs, to intersection of the rear wall, to
the side wall having the small glass window. NOTE:
Attach wall finishing to constructed frame, not
the appliance.

Framing & Finishing

Noncombustible materials such as brick or tile may be
extended over the edges of the face of the appliance.
DO NOT cover any vent or grille panels.
If a Trim Kit is going to be installed on the fireplace, the
brick or tile will have to be installed flush with the edges
of the appliance.

Max.

Min.

Input

Input

Model

Fuel

Gas Control

BTU/h

BTU/h

360DVS2RN

Nat

Millivolt

38,000

26,600

360DVS2RP Prop

Millivolt

38,000

28,500

360DVS2EN

Nat

24V Hi/Lo

38,000

26,600

360DVS2EP Prop

24V Hi/Lo

38,000

28,500

360DVS3RN

Nat

Millivolt

38,000

26,600

360DVS3RP Prop

Millivolt

38,000

28,500

360DVS3EN

Nat

24V Hi/Lo

38,000

26,600

360DVS3EP Prop

24V Hi/Lo

38,000

28,500

360DVSLRN

Nat

Millivolt

38,000

26,600

360DVSLRP Prop

Millivolt

38,000

28,500

360DVSRRN Nat

Millivolt

38,000

26,600

360DVSRRP Prop

Millivolt

38,000

28,500

Gas Specifications

Gas Inlet & Manifold Pressures

Natural

LP (Propane)

Inlet Minimum

4.5” w.c.

11.0” w.c.

Inlet Maximum

14.0” w.c.

14.0” w.c.

Manifold Pressure

3.5” w.c.

10.0” w.c.

Input ratings are shown in BTU per hour and are
certified without deration for elevations up to
4,500 feet (1,370 m) above sea level.
For elevations above 4,500 feet (1,370 m) in USA,
installations must be in accordance with the
current ANSI Z223.1/NFPA 54 and/or local codes
having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations
above 4,500 feet (1,370 m).

When purging the gas lines, the window
frame assembly must be removed.

The gas pipeline can be brought in through the vent
end of the fireplace as well as the bottom. Knockouts
(to allow gas pipe installation and testing any gas con-
nection) are provided on the bottom behind the valve.
It is most convenient to bring the gas line in from the
vent end of the valve, as this allows fan installation or
removal without disconnecting the gas line.
The gas line connection can be made with properly
tinned 3/8” copper tubing, 3/8” rigid pipe, or an ap-
proved flex connector. Since some municipalities have
additional local codes, it is always best to consult your
local authority and the CSA-B149.1 installation codes.
For USA installations, consult the current National Fuel
Gas Code, ANSI Z223.1/NFPA 54.

Always check for gas leaks with a mild
soap and water solution. Do not use an
open flame for leak testing.

The gas control is equipped with a captured-screw type
pressure test point, therefore it is not necessary to pro-
vide a 1/8” test point upstream of the control.

Gas Line Installation