360dvs series direct vent fireplaces, Vertical through-the-roof application – Majestic Appliances 360DVS3 User Manual

Page 21

Advertising
background image

21

360DVS Series Direct Vent Fireplaces

10006326

Vertical Through-the-Roof Application

This Gas Fireplace has been approved for:

Vertical installations up to 40’ (12 m) in height. Up
to a 10’ (3 m) horizontal vent run can be installed
within the vent system using a maximum of two 90°
elbows. (Fig. 30)

max height & length

360DVS

rev. 9-17-02 rjs

Max. Height 40’

(12.2m)

Min. Height 8’

(2.4m)

Max. 10’ (3m)

Support Straps

Every 36”

(914mm)

Max. 10’ (3m)

Max. Height

40’ (12.2m)

Min. Height

8’ (2.4m)

FP1443

Fig. 30 Support straps for horizontal runs.

Up to two 45° elbows may be used within the hori-
zontal run. For each 45° elbow used on the hori-
zontal level the maximum horizontal length must be
reduced by 18” (457 mm).

Example: Maximum horizontal length:

Zero elbows

= 10’ (3 m)

1 x 45° elbows = 8¹⁄₂’ (2.6 m)
2 x 45° elbows = 7’ (2.1 m)

A minimum of an 8 ft. (2.43 m) vertical rise.

Two (2) sets of 45° elbow offsets may be used within
the vertical sections. From zero to max 8 ft. (2.43 m)
vent pipe can be used between elbows. (Fig. 30)

7DVCS supports offsets. (Fig. 33) This application
will require you first determine the roof pitch and use
the appropriate starter kit. See Venting Components
List, Page 22.

The maximum angular variation allowed in the sys-
tem is 270˚. (Fig. 31)

The minimum height of the vent above the highest
point of penetration through the roof is 2’ (610mm).
(Fig. 32)

1
2
3
4

1
2
3
4

1 + 2 + 3 + 4 = 270°

FP1444

Fig. 31 Maximum elbow usage.

Min.

2' (610 mm)

FP1185

Fig. 32 Maximum termination to roof clearance.