15

360DVS Series Direct Vent Fireplaces

10006326

Fig. 14 Termination clearances.

General Information Assembling Vent Pipes

Canadian Installations:
Venting system must be installed in accordance with the

current CSA-B149.1 installation code.
USA Installations:
The venting system must conform with local codes and/
or current National Fuel Gas Code ANSI Z223.1/NFPA
54.
Only venting components manufactured by CFM Corpo-
ration can be used in Direct Vent systems.

Twist Lock Pipes

When using twist-lock pipe, it is not necessary to use
sealant on the joints. The only areas of the venting
system that need to be sealed with high-temperature
silicone sealant are the sliding joints of telescopic vent
sections used in the system.

To join the twist lock pipes together, align the beads
of the male end with the grooves of the female end.
While bringing the pipes together, twist the pipe until the
flange on the female end contacts the external flange
on the male end. It is recommended that you secure the
joints with three (3) sheet metal screws; however, this is
not mandatory with twist lock pipe.
NOTE: For ease of assembly, use a lubricant (Vaseline
or similar substance) on male end of twist lock pipe
prior to assembly.

Male End

Female End

Screw Holes

TWL100

Fig. 15 Twist lock pipe joints.

Outside Corner

Inside Corner

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

G =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

F =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

G

Balcony -

with no side wall

M =
Combustible &
Noncombustible
12" (305 mm)

M

Balcony -

with perpendicular side wall

M = 24" (610 mm)
P = 20” (508 mm)

M

F

Alcove Applications*

C

D

C

E

V

V

Combustible &

Noncombustible

V

V

V

E

= Min. 6” (152 mm) for

non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls

O

= 8’ (2.4 m) Min.

O

P

584-15

No.

of Caps

D

Min.

C

Max.

1

3’ (914 mm) 2 x D

Actual

2

6’ (1.8 m)

1 x D

Actual

3

9’ (2.7 m)

2/3 x D

Actual

4

12’ (3.7 m) 1/2 x D

Actual

D

Min.

= # of Termination caps x 3

C

Max.

= (2 / # termination caps) x D

Actual

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.