360 dvs series direct vent fireplaces, Below grade installation – Majestic Appliances 360DVS3 User Manual

Page 20

Advertising
background image

20

360 DVS Series Direct Vent Fireplaces

10006326

2” (51 mm). Secure termination to the wall with screws
provided, and caulk around the wall plate to weather-
proof.
One alternative to screwing the termination directly to
the wallis the use of expanding plugs or an approved
exterior construction adhesive.
Or, you may attach the termination with screws through
the inner body into the 4” (102 mm) vent pipe; however,
for this method, you must extend the 4” (102mm) pipe
approximately 6” (153 mm) beyond the outer face of the
wall.

Support the horizontal pipes with metal
pipe straps every 36” (914mm).

Below Grade Installation

When it is not possible to meet required vent terminal
clearances of 12” (305 mm) above grade level, we rec-
ommend using a starter kit. It allows installation depth
down to 7” (178 mm) below grade level. Measure 7”
(178 mm) from the center of the horizontal vent pipe as
it penetrates through the wall.
NOTE: Ensure sidewall venting clearances are ob-
served. If venting system is installed below ground,
we recommend a window well with adequate and
proper drainage.
If installing a snorkel, a minimum 24” (610 mm)
vertical rise is necessary. The maximum horizontal
run with 24” (610 mm) vertical pipe is 36” (914mm).
The measurement is taken from the collar of the
fireplace (or transition elbow) to the face of exterior
wall. See sidewall vent graph, Page 15, for extended
horizontal runs if the vertical exceeds 24” (610 mm).
1. Establish vent hole through the wall. (Fig. 24)
2. Remove soil to depth of about 16” (406 mm) below

base of snorkel. Install window well (not supplied).
Refill hole with 12” (305 mm) of coarse gravel, leav-
ing a clearance of about 4” (102 mm) below snorkel.
(Fig. 28)

3. Install vent system.
4. Ensure a watertight seal is made around the vent

pipe coming through the wall.

5. Apply high-temperature sealant caulking (supplied)

around 4 in. and 7 in. snorkel collars.

6. Slide snorkel into vent pipes and secure to wall.
7. Level the soil so as to maintain a 4” (102 mm) clear-

ance below snorkel. (Fig. 29)

Zero Clearance

Sleeve (if required)

Firestop

7” Pipe

24” (610mm)

Minimum

Screws

7TDVSNORK

(Snorkel)

Min. 4” (102mm)

Clearance

(Ground)

Window Well

Gravel

Foundation Wall

Drain

A minimum of 24” (610mm)

vertical pipe must be installed

when using the 7TDVSNORK

Kit.

The 22” (559mm) vertical rise

(center to center) of the snorkel

may be included for calculation

of maximum horizontal run.

FP1442

Fig. 28 Below grade installation.

Do not backfill around the snorkel. A clear-
ance of at least 4” (102mm) must be main-
tained between the snorkel and the soil.

If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fas-
ten brackets to wall first, then secure to snorkel with self
drilling #8 x 1/2 sheetmetal screws. It will be necessary
to extend vent pipes out as far as protruding wall face.
(Fig. 29)

CFM139

Snorkel

2/26/01 sta

rev. 9-25-02 rjs

Snorkel

Foundation Wall

Watertight Seal

Around Pipe

Wall Screws

Sheet Metal Screws

CFM139

Fig. 29 Snorkel installation / recessed foundation.