MITSUBISHI ELECTRIC WT03939X20 User Manual

Page 101

Advertising
background image

100

Select one of the following operations by clicking a radio button.

* The pressed (sunken) button shows the currently “Enabled” status.


* [DIDO operation]

Select the channel to be output, and set whether to [Operation] or [Stop] the selected channel.

* [ON/OFF]

Set the start/stop control of the indoor unit.
Even when the LOSSNAY unit is not interlocked with the indoor unit, one of the operation mode
buttons of [Interlocked LOSSNAY unit] must be set to “Enabled”.

* [Mode]

Set the operation mode of the indoor unit.

* [Set temp.]

Set the set temperature of the indoor unit.






(8) Click [OK].

(9) The screen will return to the DIDO controller (66DC) Interlock control setting screen.
(* The settings have not been saved yet.)

(10) Repeat the steps between (6) and (9).


(11) Select the [Disable] or [Output] of each

channel for each setting item,
[Emergency stop receive: Interlock
disable],
[SC communication error detection:
Interlock disable]
and
[Interlock operation error: Error report
output]
.

(12) Click [Send settings].



(13) ”Settings will be sent. OK?”

will appear, click [Yes].
The setting will be applied to the unit.


(14) ”Settings have been sent.”will appear, click [OK].

(15) Click [Close] to return to the Main screen.

Caution:

Only make the interlock settings for the functions that are supported by the unit to be interlocked.
Making the interlock setting for functions that are not supported may result in malfunctions or failures.

NOTE:

When you use Fahrenheit for the unit, there might be differences of the plus or minus 0.1 °F in the set
value and the value monitored after it sets it.