2 setting and monitoring ai controllers (63mc) – MITSUBISHI ELECTRIC WT03939X20 User Manual

Page 83

Advertising
background image

82

3.13.2 Setting and Monitoring AI Controllers (63MC)

AI Controller (PAC-YG63MCA) is capable of measuring the temperature and humidity.
Trend displays of measurement data can be shown on the G(B)-50A Web Browser and TG-2000A.
Furthermore, an alarm can be output if measurement data exceeds a preset upper or lower limit.




















The function allotment of AI Controller, G(B)-50A Web Browser,TG-2000A and Maintenance Tools is as
follows.

[Note] S:Setting possibility, M:Monitoring only, -:None

Function name

AI Controller

G(B)-50A

Web

TG-2000A Maintenance

Tools

Address setting

S

*1

-

- M

Setting of the input to use

S

*1

-

- M

Setting of the analog input
type

S

*1

-

- M

Range and category
setting of sensor

- S

S M

(Operation is possible)*2

Setting of upper/lower limit
alarm interlock output use

S

*1

-

- M

Range setting of
Upper/Lower limit alarm

- S

S M

(Operation is possible)*2

Monitoring and trend
displays of measurement
data

- S

S M

(Monitoring only)

Time setting

-

S

S

M

(Operation is possible)*2


Temperature sensor,
Humidity sensor, etc

Max.

Temperature 1
Humidity 1

(3)(4)

(1)(2)

(1) Channel 1 temperature or humidity sensor input
(2) Channel 2 temperature or humidity sensor input
(3) Channel 1 upper/lower limit alarm output
(4) Channel 2 upper/lower limit alarm output

Hub

G(B)-50A

Outdoor unit

Indoor units

M-NET

M-NET

AI controller

TG-2000A

24 VDC
Power supply

G(B)-50A Web

*1 It is set with Dip switch of AI Controller.
*2 When G(B)-50A or TG-2000A is connected, the setting must be made on G(B)-50A Web Browser or TG-2000A.

Advertising