MITSUBISHI ELECTRIC WT03939X20 User Manual

Page 85

Advertising
background image

84

3.13.2.2 Setting for AI Controllers (63MC)









(1) Click [Setting contents] in the AI controller

(63MC) measurement value monitoring
screen
.









(2) The setting details are monitored, and, AI controller (63MC) setting screen will appear.

[Category]

The measurement category (temperature or
humidity) is shown.

[Upper limit value][Lower limit value]

The upper/lower limits of the measurement
range are shown.

<Settable range>
In case of temperature:-100.0°C to 100.0°C

(-148.0°F to 212.0°F)

In case of humidity:0.0% to 100.0%
Note that the range must be fixed between
–30.0°C and 60.0°C (-22.0°F and 140.0°F)
when the temperature sensor for Pt100 detection

(Ch1 only) is used.

[Correction value]

The correction value is shown.
< Settable range >

In case of temperature:-10.0°C to 10.0°C (-18.0°F to 18.0°F)

In case of humidity:-10.0% to 10.0%

[Upper limit alarm detection] [Upper limit alarm cancellation]
[Lower limit alarm cancellation] [Lower limit alarm detection]

The alarm detection value and the alarm cancellation value are shown.

[Time setting]

The current date and time is shown.

(3) Check the checkbox of the channel to be output and

the check box of [Time setting] (when time setting is needed).

(4) Change the settings.

(5) Click [Send settings].

NOTE:

When G(B)-50A or TG-2000A is connected, the setting must be made on G(B)-50A Web Browser

or

TG-2000A.
When the settings are made on Maintenance Tools, the setting change is not applied to G(B)-50A or
TG-2000A.