15. electrical service guide – Miller Electric 1000 User Manual

Page 26

Advertising
background image

OM-2221 Page 22

3-15. Electrical Service Guide

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-

tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.

Three-Phase, 50/60 Hz

Three-Phase, 60 Hz

Input Voltage

380

400

415

500

460

575

Input Amperes At Rated Output

149

141

136

113

123

98

Max Recommended Standard Fuse Rating In Amperes

1

Time-Delay

2

175

175

150

125

150

110

Normal Operating 3

225

200

200

175

175

150

Min Input Conductor Size In AWG 4

1/0

1/0

1/0

2

1

3

Max Recommended Input Conductor Length In Feet (Me-

ters)

398 (121)

441 (134)

474 (145)

490 (149)

482 (147)

548 (167)

Min Grounding Conductor Size In AWG 4

4

6

6

6

6

6

Reference: 2005 National Electrical Code (NEC) (including article 630)

1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” .

3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.