Multitec, 6commissioning, start-up / shutdown – Multitech 1777.8/7-10 G3 User Manual

Page 11

Advertising
background image

Caution

Caution

Caution

Pump sizes

32 to 100

Pump sizes

125 and 150

Caution

Multitec

11

6

Commissioning, start-up / Shutdown

Instructions for boiler feed applications
Limit values for boiler feed water and condensate when using

cast iron pump parts: pH value ³ 9.0 (target: ³ 9.3)

O

2

content

0.02 ppm.

These values must be ensured under all operating conditions

before entry into the pump. Max. percentage of fresh water:

25%.

Water treatment shall be in accordance with VdTÜV guidelines

for feed and boiler water in steam plants of up to 64 bar.

The penetration of air into the system must be avoided by all

means.
6.1

Commissioning

Before starting up the pump make sure that the

following requirements have been met:

- The quality of the concrete foundation is in compliance with

the applicable regulations.

- The tolerances stipulated for mounting the unit on the

foundation, for shims and alignment have been complied

with.

- The pipelines have been connected without warping the

pump nozzles.

- Electrical connection and relay settings correspond to the

motor rating and comply with the applicable regulations.

- All hydraulic, electrical and mechanical protection devices

have been set.

- The pump has been fully primed with the fluid to be pumped.

- The unit’s direction of rotation corresponds to the rotation

arrows.

- All connections are leak-free.

For installation without foundation (e.g. on spring

elements) care must be taken that all movements

of the pump unit can be compensated, e.g. by fitting expansion

joints in the discharge and suction lines.
6.1.1 Lubricants
Grease-lubricated bearings

The grease-lubricated bearings are packed with grease at the

factory (see section 7.2.2).

Oil lubricated bearings

Fill oil of ISO VG 46 quality into the bearing cover (see section

7.2.2).
6.1.2 Priming the pump and checks to be carried out
Before each start-up, the pump and the suction line must be

completely vented and primed with the fluid to be pumped. The

pump has several plugged holes for venting; adequate venting

devices can be used in the pipelines. The shut-off valve in the

suction or feed line must be fully open.

Fully open all auxiliary connections provided and check the

throughflow.

Open shut-off valve ”C” in the vacuum balance line (if any), and

close the vacuum-tight shut-off valve ”E” (see 5.4.1).

Dry running will lead to increased wear on the unit

and may eventually damage the pump !

If the discharge line is equipped with an automatic check valve,

open the minimum flow valve and secure against inadvertent

closing.

Exceptions:

- If there is not enough back pressure in the line prior to

start-up, the shut-off element must be closed before pump

start-up.

- On pumps fitted with a mechanical seal, the mechanical seal

will leak only slightly, i.e. practically invisibly (vapour) during

operation. It is maintenance-free.

- If the pump is equipped with a gland packing, leakage during

operation is normal (see 6.1.6).

Special notes regarding cooled mechanical seals

(seal code 64)
- If the pump is equipped with a cooled mechanical seal, vent

the seal chamber by opening the screwed plug 903.11 by a

quarter turn, then re-tighten.

Fig. 14

Fig. 15

The seal chamber has to be vented when the

pump is in cold condition before start-up. When

venting in hot condition, steam will escape at the vent plug

during the venting process (risk of scalding!) Should it not be

possible to avoid opening the seal chamber in hot condition,

due to the situation in the plant, a pipe with valve (not included in

KSB’s scope of supply) must be installed at the vent hole, in

order to lead the steam escaping during venting to another

place where there is no danger of scalding. Make sure that this

valve cannot be opened during operation.

Advertising