Multitec – Multitech 1777.8/7-10 G3 User Manual

Page 13

Advertising
background image

Caution

Caution

Multitec

13

6.2.2 Switching frequency

The permissible number of start-ups in a given period of time

depends on the circumstances prevailing in the plant and the

operating conditions. Overloading of the motor may generally

result in:

- an abnormal increase in motor temperature exceeding the

temperature limit of the winding or bearing grease

- premature coupling wear

- reduced service life of the pump components

- irregularities or malfunctions in the plant

To prevent abnormal temperature increases in the motor and

excessive loads on the motor, coupling, pump, seals and

bearings, the switching frequency must not exceed the

following number of start-ups per hour (h):

Motor rating

Max. start-ups/h

up to 3 kW

from 4 to 11 kW

from 11 to 45 kW

45 kW and higher

20

15

10

5

6.2.3 Minimum flows

The pump must not be operated against a closed gate valve.

The minimum flows required are defined as follows.
For MTC 32, MTC 50 and MTC 65, the required minimum flow

for continuous operation is:
t

-10 to + 100 °C

15 % of Qopt

t > 100 to + 140 °C

20 % of Qopt

t > 140 to + 200 °C

25 % of Qopt

For MTC 100, MTC 125 and MTC 150, the minimum flow

required for continuous operation, independent of the

temperature, is:

0.35 x Qopt.

For MTC 100, MTC 125 and MTC 150 an additional, short--term

minimum flow of 0.25 x Qopt. has been defined, which is

permitted for up to 1 hour’s uninterrupted operation and approx.

200 h/year.

The minimum flows indicated for MTC 32 to 150 above are for

single pump operation and will prevent thermal and mechanical

overloading of the pump. In case of parallel operation with

pumps of identical or different design higher flow rates may be

required in some cases, to guarantee a stable operating

behaviour.

6.2.4 Density of fluid pumped

The pump input power will increase in proportion to the density

of the fluid handled. To avoid overloading of the motor and

pump, the density of the fluid must comply with the data

specified on the purchase order.

6.3

Shutdown / Storage / Preservation

6.3.1 The unit / pump remains installed; periodic check of

operation

In order to make sure that the pump is always ready for instant

start-up and to prevent the formation of deposits within the

pump and the pump intake area, start up the pump set regularly

once a month or once every 3 months for a short time (approx. 5

minutes) during prolonged shutdown periods. Follow the

instructions for commissioning (see 6.1).

Prolonged shutdown periods should be avoided in the case of

pumps in material variants 10, 13, 20 and 21 (cast-iron

variants), particularly if the pumps are handling aggressive

water qualities (high oxygen content). In such cases, the pump

should remain filled, and the operation check run should be

performed at least every other day, instead of once a month or

once every 3 months (see also 6.1.5).

In the event of frost and/or prolonged shutdowns, the pump

must be drained and protected against freezing and corrosion.

To drain the pump, open drain plug 6B.

In the case of horizontal pumps, virtually

complete drainage of the stage casings in

installed condition can only be ensured by opening the plugs on

the stage casings (optional). If this is not possible, it is

recommended to remove the pump from the system and

proceed according to section 6.3.2.
6.3.2 The pump is removed from the pipe and stored

Before putting the pump into storage, carry out all checks and

maintenance work specified in section 7.1. Then preserve as

follows:

Drain the pump as completely as possible. On vertical pumps,

this can be done by opening the drain plugs on the suction

casing.

Horizontal pumps with drain holes in the stage casings

(optional) can be drained almost completely by opening the

drain plugs. The pump can also be drained by bringing it into a

vertical position - suction nozzle pointing downwards - by crane

(see 3.1). Turn the rotor by hand. However, the seal housing

must still be drained separately by opening the respective drain

plug.

If the pump cannot be drained completely, we

recommend to dismantle it and dry the individual

components.

Afterwards fill the pump with a water-repellent preservative, e.g.

RUSTELO DEWATERING 924 (producer CASTROL)

OSYRIS DW (producer TOTAL) or equivalent.

Turn the pump rotor by hand several times, to ensure even

distribution of the preservative. Then drain the pump and close

the suction and discharge nozzle.
Exposed blank metal parts must be treated with a suitable

anti-corrosive agent.

If the pump is preserved for a prolonged storage

period with KLÜBERTOP K 01-601 or another

glycol-base preservative, the preservative must not be drained.

In this case, the pump must be completely filled with

preservative for storage. The preservative must be drained

before the pump is returned to service. It can be re-used. Before

re-use, make sure that the water content in the preservative

does not exceed 20%.
6.4

Returning to service after storage

Before returning the pump to service, carry out all instructions

laid down in the sections on ”Commissioning” (6.1) and

”Operating limits” (6.2).

Immediately

following

completion

of

the

work,

all

safety-relevant and protective devices must be re-installed

and/or re-activated.

Advertising