Multitec – Multitech 1777.8/7-10 G3 User Manual

Page 12

Advertising
background image

Caution

Caution

Multitec

12

6.1.3 Contact guard

In compliance with health and safety regulations the

pump must not be operated without a coupling guard. If

the customer specifically requests not to include a coupling

guard in our delivery, then the operator must supply one.
6.1.4 Connection to power supply

If the pump is equipped with an electric motor, connection to the

power supply must be effected by a trained electrician only.

Check available mains voltage against the data on the motor

rating plate and select appropriate start-up method.

Make sure that in the case of three-phase motors with star-delta

starting method switching over from star to delta will be effected

at very short intervals. Prolonged switch-over intervals will

result in pump damage.

Time relay setting for star-delta starting

Motor rating

Y time to be set

≦ 30 kW

> 30 kW

3 sec. ± 30 %

5 sec. ± 30 %

6.1.5 Start-up
Start-up procedure

- The discharge-side shut-off valve must be closed.

- Start-up must proceed without abnormal vibrations or

noises.

- An automatic check valve installed must open steadily when

the operating speed has been reached, without abnormal

noise, vibrations or increased power consumption of the

unit.

- Open the discharge-side shut-off valve.

- After the duty point has been reached, check motor input

power and bearing temperature.

After the operating temperature has been reached, switch off

the pump and re-tighten the bolts at the connecting flanges.

In the event of abnormal noise, vibrations,

temperatures or leakage, switch off the unit

immediately and re-start it only after the cause for the problem

has been eliminated.

Increased temperatures at the rolling element bearings after

commissioning are caused by the running-in process. The final

bearing temperature will be reached only after a certain

operating period (up to 48 h, depending on operating

conditions).

6.1.6 Shutdown
Close the shut-off valve in the discharge line.

If the discharge line is equipped with a non-return or check

valve, the shut-off element may remain open if there is sufficient

backpressure.

- Switch off the motor, making sure that the unit runs down

smoothly to a standstill.

- For prolonged shutdown, close the shut-off valve in the

suction line. Also close the auxiliary feed lines.

- The shaft seal in pumps where the liquid is fed in under

vacuum must also be supplied with barrier liquid during

standstill.

- In the event of frost and/or prolonged shutdowns, the pump

must be drained or otherwise protected against freezing.

If the pump has to remain operational during shutdown periods,

it must be started up regularly for at least 5 minutes (see also

6.3):

- fire-fighting pumps at least once a month

- drinking water pumps at least once in 48 hours

- stand-by pumps at least once a week

(It is better to operate the pumps by alternating daily.)

During these periodic check runs also check the integrity and

proper functioning of the auxiliary feed lines.
6.1.7 Final check

After the pump has been primed, it must be easy to rotate the

coupling/ shaft by hand.

There must be no impermissible leakage at the shaft seal

during pump operation.
Gland packing

The gland packing has been fitted in the factory. Its permanent

compression can only be set after several hours of pump

operation. During this running-in period, gland leakage will be

higher than during normal pump operation. Check the

temperature of the leakage.

Final adjustment of the gland packing is made gradually after

having allowed for a sufficient running-in period, so that leakage

is reduced to individual drops (approx. 20 drops per minute).

Tightening the gland cover too early or too hard without allowing

for a sufficient running-in period would cause a local

temperature rise and insufficient lubrication, resulting in the

destruction of the gland packing, premature wear on the shaft

protecting sleeve and higher, uncontrollable leakage.
For speed controlled pumps or fluctuating inlet pressure, no

gland packing should be used, if possible. Changing pressures

make it difficult to set an even and controlled leakage rate.

Should such conditions occur, leakage of the

gland packing must not be prevented under any

operating conditions. At increased inlet pressure and/or

increased speed, the inevitably higher leakage of the gland

packing must not be reduced by re-tightening the gland bolts.

The minimum leakage rate must only be set at the lowest speed

and/or lowest inlet pressure.
Mechanical seal

The mechanical seal assembly has been adjusted and installed

in the factory. It is maintenance-free. Check the seal for leakage

occasionally.

During commissioning, increased leakage may occur for a

short period of time. If leakage remains high, immediately

switch off the pump and investigate the leakage cause, e.g.

contaminated fluid handled or previous dry running due to

inadequate venting of the pump unit.
Cooled mechanical seal (seal code 64)

If the pump is fitted with a cooled mechanical seal (seal code

64), vent the seal chamber as described in 6.1.1.
6.2

Operating limits

The hydraulic system is designed for pure or slightly

contaminated liquids (max. solids content: 20 ppm). Make sure

that the operating limits indicated in the order confirmation are

complied with.
6.2.1 Temperature of the fluid pumped

The pump must not be operated at temperatures exceeding

those specified on the name plate or in the technical data sheet.

Advertising