Extended parameter setting – Magnetek 188-10130 User Manual

Page 26

Advertising
background image

RVS-DX, Digital Soft Starter Instruction Manual—04/01/04
4-6

Extended Parameter Setting

The RVS-DX incorporates a parameter, “WIDER SETTINGS”, in the special Features Parameters.
If the RVS-DX is significantly larger than your motor, you can enable the “wider settings” to extend
parameter settings of the following:

Extended Parameter Settings

Parameter

Original Setting Range

Extended Setting Range

Initial Voltage

10-50%

10-80%

Current Limit

100-400%

100-500%

Acceleration Time

1-30 seconds

1-90 seconds

Deceleration Time

0-30 seconds

0-90 seconds

Max. Start Time

1-30 seconds

1-250 seconds

Advertising