RVS-DX, Digital Soft Starter Instruction Manual—4/01/04
6-8

FAULT PARAMETERS (display mode set to maximized to access)

Parameter

Description/Function

Default Value

Range

Access

PHASE SEQ. Y/N

INSULATION ALARM

INSULATION TRIP

AUTO RESET

THERMISTOR TYPE

THERMISTOR TRIP

UNDER CUR. RESET

STORE ENABLE

FAULT PARAMETERS

Phase sequence trip setting
Insulation alarm setting
Insulation trip setting
Auto reset 'on/off' setting
Thermistor type setting
Thermistor trip setting
Under current auto reset time setting
Press 'Store' to save changes made to any of the

Fault Parameters

NO

OFF
OFF

NO

PTC
OFF
OFF

Yes=on; No=off

off; 0.2-5 Mohm
off; 0.2-5 Mohm

Yes=on; No=off

PTC, NTC

off; 0.1-10.0 Kohm

10-120 min.; off

maximized
maximized
maximized
maximized
maximized
maximized

I/O PROGRAMMING PARAMETERS (display mode set to maximized to access)

Parameter

Description/Function

Default Value

Range

Access

PROG.INPUT C1

FAULT RELAY TYPE

PROG. AUX. RELAY

RELAY ON DELAY

RELAY OFF DELAY

ANALOG OUTPUT

STORE ENABLE

I/O PROG. PARAM

Sets terminal C1 to: Dual adjust, generator mode,

slow speed/reverse, external fault, remote reset.

Fault
Fault-fail safe

Immediate or End of Accel

Time Delay before relays turns on
Time Delay before relay turns off

Normal=output increases with increasing current
Inverted=output increases with decreasing current

Press 'Store' to save changes made to any of the I/

O Programming Parameters

Remote Reset

Fault

Immediate

0
0

Normal

Dual Adjustment,

Generator mode, slow

speed/rev., external

fault, reset

Fault, Fault-Fail Safe

Immediate, End of

Accel.

0-60 seconds
0-60 seconds

Normal, Inverted

maximized

maximized

maximized

maximized
maximized

maximized

COMMUNICATION PARAMETERS (display mode set to maximized to access)

Parameter

Description/Function

Default Value

Range

Access

COMM. PROTOCOL

DRIVE NUMBER

BAUD RATE

PARITY CHECK

SERIAL LINK NO.

STORE ENABLE

COMM.PARAMETERS

Serial Communicaitons protocol selection
Drive number setting
Baud rate setting
Parity Check setting
Serial link number
Press 'Store' to save changes made to any of the

Communication Parameters

Modbus

0

9600
Even

248 (off)

Modbus, Profibus

0-999

1200, 2400, 4800, 9600

Even, Odd, NO

1-248

maximized
maximized
maximized
maximized
maximized