Magnetek 188-10130 User Manual

Page 39

Advertising
background image

RVS-DX, Digital Soft Starter Instruction Manual—4/01/04

6-3

Mode

Mode

Mode

Mode

Mode

Upon Initiation

Parameter Display

Page 1

Page 2

Page 3

Page 4

Select

Select

Select

Select

Select

% Of Motor FLA

Main Parameters

Start Parameters

Stop Parameters

Dual Adj. Parameters

To Review All

Parameters

Press

Keys To Change Parameter Value

Option Card Not
Installed

BACK TO TOP

Starter FLC
105 Amp

Motor FLA
105 Amp

Undercurr. Trip
0% Of FLA

Undervolt. Trip
75%

O/C Shear Pin
850% Of FLA

Overload Trip
115% of FLA

Overload Delay
4 Sec.–at 5 FLA

Undervolt.
Delay 5 Sec.

Under Curr.
Delay 10 Sec.

Overvolt. Trip
120%

Overvolt. Delay
2 Sec.

Store Enable
Main Parameters

BACK TO TOP

Soft Start Curve
0 (Standard)

Start Tacho Gain
0 (Min. Gain)

Pulse Time
0 Sec.

Initial Voltage
30%

Current Limit
400% of FLA

ACC. Time
10 Sec.

Max. Start Time
30 Sec.

Number of Starts
10

Starts Period
30 Min.

Start Inhibit
15 Min.

Store Enable
Start Parameters

Soft Stop Curve 0
(Standard)

Stop Tacho Gain 0
(Min. Gain)

Final Torque
0 (Min)

Dec. Time
0 Sec.

Store Enable
Stop Parameters

DA: (Generator)
Parameters

DA: Int. Volt
30%

DA: Cur. Limit
400% of FLA

DA: Acc. Time
100 Sec.

DA: Dec. Time
0 Sec.

DA: Motor FLA
105 Amp

Store Enable D.
Adj. Parameters

BACK TO TOP

BACK TO TOP

BACK TO TOP

When DIP SW#1.2 is set ON

When Prog. Input C! is set to
Generator Start/Stop

Initial Current
100%

DA: Int. Current
100%

Note: Available after
initial voltage setting
is above maximum level.

Connection Type
Line

Rated Line Volt.
460 Volt

O/C Delay
0.5 Sec.

Display Mode
Minimized

Parameters Lock
Not Locked