Troubleshooting – Magnetek 188-10130 User Manual

Page 54

Advertising
background image

RVS-DX, Digital Soft Starter Instruction Manual—4/01/04

8-3

Troubleshooting

Upon fault the motor stops, “Fault” LED illuminates and fault relay operates. The LCD will display
“Trip: fault description”.

Check “Statistical Data” for additional fault-related information.

Fault

Description

ALARM: INSULATION

(Optional) Initiates a signal when motor insulation level decreases below set level.

TRIP: INSULATION

(Optional) Trips the starter when motor insulation level decreases below trip value.

Check motor and cable insulation level.

TRIP: THERMISTOR

(Optional) Trips the starter when motor’s thermistor resistance decreases below trip

value. Check thermistor and cable’s resistance; check motor temperature near

thermistor location.

TOO MANY STARTS

Trips the starter if the number of starts during “Start Period” exceeds the preset

number. Wait until motor and starter cool down–according to “Start Inhibit” setting.

LONG START TIME

Trips the starter if output voltage does not reach nominal at the preset time. Check

“FLA”, “FLC” and “Max. Start Time” settings. Increase “Initial Voltage”, “Current

Limit” and “Max. Start Time” settings or decrease “Acceleration Time” as necessary.

O/C–SHEAR PIN

The electronic fuse trips the starter instantaneously when current exceeds 8.5 X FLA

during starting or 200-850% during running. Check “FLA”, “FLC” settings, motor

and cable connections. Check that the motor is not stalled.

OVERLOAD

Trips the starter when current exceeds the Overload Trip level and thermal register has

filled up. Check “FLA”, “FLC” and “Overload” settings, and check the motor current.

Wait 15 minutes to let the motor and stater cool down before starting.

UNDERCURRENT

Trips the starter when line current drops below the preset level for the preset time.

Check “Undercurrent Trip” and “Undercurrent Delay” settings. Check line current

through L1, L2, and L3.

UNDERVOLTAGE

Trips the starter when line voltage drops below the preset level for the preset time.

Check “Undervoltage Trip” and “Undervoltage Delay” settings. Check line voltage

through L1, L2 and L3.

OVERVOLTAGE

Trips the starter when line voltage rises above the preset level for the preset time.

Check “Overload Trip” and “Overvoltage Delay” settings. Check line voltage through

L1, L2 and L3.

PHASE LOSS

Trips the starter if 1 or 2 phases are missing. Check line voltages through L1, L2 and

L3. Check that the frequency variations are between 45 to 65 Hz.

PHASE SEQUENCE

Trips the starter if input phase sequence is wrong. Check line phase sequence and if

wrong, swap two wires on the line side. If the motor rotates in the wrong direction,

swap two wires on the load side.

MAX. SLOW SP TIME

Trips the starter when operating at slow speed for extended period of time. Check that

operation time at Slow Speed is shorter than the “Max. Slow Speed Time” setting.

NOTE: Motor and starter may overheat when operating at slow speed for an extended

period of time.

WRONG CONNECTION

Trips the starter when motor is not properly connected to load terminals.

SHORTER SCR

Trips the starter and prevents starting if one or more SCRs are short circuited or when

motor windings are shorted. Check with an ohmmeter between L1-U, L2-V and L3-W,

resistance > 20 K

Ω.

SCRs may fail due to:

• High short current not protected by proper fuses.
• High voltage spikes not protected by proper external varistors.
• Frequent starting at max. conditions or fault conditions.

OVERTEMPERATURE

Heatsink overtemperature. Trips the starter when the heatsink temperature rises above

85°C. Improve cooling. Check the motor staring is not too frequent.

EXTERNAL FAULT

Trips the starter when a N.O. contact between terminal A2 and C1 closes for over two

seconds. Check contact position and cause of closure.

Advertising