RVS-DX, Digital Soft Starter Instruction Manual—4/01/04

A-3

RVS-DX Technical Data/Specifications

General Information:

Supply Voltage

Line to Line 220-600V (to be specified) +10%, -15%

Frequency

45-65Hz (fixed or variable source)

Control Supply

110-120V +10%, -15%

Control Inputs & Outputs

110-120V

Load

Three phase, three wire, squirrel cage induction motors

Stop Parameters:

Start FLC

Starter’s full load current

Motor FLA

Motor’s full load amps, 50-100% of starter FLC

Pump Control Curves

6 field selectable curves to prevent over-pressure and water hammer

Pulse Start Duration

A pulse of 80% voltage for an adjustable time of 0.1-1 second, for starting high

friction loads

Initial Voltage

10-50% voltage (can be extended to 10-80%)

Current Limit

100-400% of motor FLA (can be extended to 100-500%)

Acceleration Time

1-30 seconds (can be extended to 1-90 seconds)

Deceleration Time

0-30 seconds (can be extended to 0-90 seconds)

Dual Adjustments

Secondary settings for: Motor FLA, Initial Voltage, Current Limit, Acceleration

Time and Deceleration Time

Slow Speed Torque

Torque while the motor is operating at 1/6 speed

Motor Protection:

Too Many Starts

Maximum allowable number of starts, range: off, 1-10; during time period of 1-60

minutes

Start Inhibit

Time period of 1-60 minutes during which starting is prevented after the “TOO

MANY STARTS” fault

Long Start Time (Stall Protection) Maximum allowable starting time 1-30 seconds (can be extended to 1-250

seconds)

Overcurrent (Shear Pin)

Two operating functions: during starting trips and starter at 850% and during

running at 200-850% current, both within 1 cycle.

Electronic Overload (I

2

T)

Adjustable 75-150% of motor FLA, adjustable trip time at 500% current of 1-10

seconds

Undercurrent

Trips when current drops below 20-90% current for time delay of 1-10 seconds

Undervoltage

Trips when main voltage drops below 50-90% for a time delay of 1-10 seconds

Overvoltage

Tips when main voltage increases above 110-125% for a time delay of 1-10

seconds

Phase Loss (Under/Over

Frequency)

Trips when one or two phases are missing and when frequency is not between 40

and 65 Hz

Phase Sequence

Trips when phase sequence is wrong

Long Slow Speed Time

Trips if operating at slow speed for more than 1-30 seconds

Wrong Connection

Prevents starting; Trips if motor is not connected or incorrectly connected to the

starter

Shorted SCR

Trips is case one or more SCR’s have been shorted

Heatsink Overtemperature

Trips when heatsink temperature rises above 85°C

External Fault

Trips when an External Control closes for 2 seconds