RVS-DX, Digital Soft Starter Instruction Manual—4/01/04
6-6

The User access level is always available. The maximized access is available when Dispaly Mode parameter is
set to maximized (changing available parameters from minimized to maximized level), but these parameters
can only be changed when the RVS-DX is stopped.

MAIN PARAMETERS

Parameter

Description/Function

Default Value

Range

Access

LANGUAGE

STARTER FLC

MOTOR FLA

CONNECTION TYPE

RATED LINE VOLT.

UNDERCURR. TRIP

UNDERCURR. DELAY

O/C—SHEAR PIN

O/C DELAY

OVERLOAD TRIP

OVERLAD DELAY

UNDERVOLT. TRIP

UNDERVOLT. DELAY

OVERVOLT. TRIP

OVERVOLT. DELAY

DISPLAY MODE

PARAMETER LOCK

STORE ENABLE

MAIN PARAMETERS

Language the Parameters are viewed in

Full load current of the RVS-DX starter
Full load amps of the motor
Determines how the soft starter will be
connected
Rated input line voltage
Under current trip setting
Under current delay setting
Over current (shear pin) trip setting
Over current (shear pin) delay setting
Overload trip setting
Overload delay setting at 500% of mtr FLA
Under voltage trip setting
Under voltage delay setting
Over voltage trip setting
Over voltage delay setting
Determines the parameters available to view.

Locks all parameters from being changed.
Press 'Store' to save changes made to any of

the Main Parameters

English

(1)
(1)

LINE

460

0%

10

850

.5

115

4

75%

5

120%

2

MINIMIZED NOT

LOCKED

English, French,

German & Spanish

8-390 amps

50-100% of FLC setting

Line or Inside Delta

220-600 V

0; 20-90% FLA

1-40 seconds

100-850% FLA

0-5 seconds

75-150% FLA

1-10 seconds

50-90%

1-10 seconds

110-125%

1-10 seconds

Minimized or

Maximized

Locked or not locked

user
user
user
user

user
user
user
user
user
user
user
user
user
user
user
user
user

START PARAMETERS

Parameter

Description/Function

Default Value

Range

Access

SOFT START CURVE

START TACHO GAIN

PULSE TIME

INITIAL VOLTAGE

INITIAL CURRENT

CURRENT LIMIT

ACC. TIME

MAX. START TIME

NUMBER OF STARTS

STARTS PERIOD

STARTS INHIBIT

STORE ENABLE

START PARAMETERS

Determines the soft start curve
Allows tach. curves after scrolling through soft start curves
Pulse (of 80% voltage) start time setting
Initial voltage setting
Allows initial current setting after scrolling through Initial
Voltage settings
Current limit setting
Acceleration time setting
Maximum starting time setting
Maximum number of starts setting
Period of time for max. number of starts
Time Delay after max. number of starts were made

Press 'Store' to save changes made to any of the Start

Parameters

0(standard)

0

30

400

10
30
10
30
15

0-4
0-5

0-1 second

10-50% (80%)(3)

100-400%

100-400% (500%)

1-30 sec. (90 sec.)(3)

1-30 sec. (250 sec.)(3)

off; 1-10

1-60 minutes
1-60 minutes

user

user(2)

user
user
user

user
user
user
user
user
user