Overview, Starter selection – Magnetek 188-10130 User Manual

Page 9

Advertising
background image

RVS-DX, Digital Soft Starter Instruction Manual—04/01/04

1-3

Overview

The RVS-DX is a digital electronic soft starter, incorporating six SCR’s to start a three phase squirrel
cage induction motor by supplying a slowly increasing voltage, providing soft start and smooth
stepless acceleration, while drawing the minimum current necessary to start the motor. The RVS-DX
is equipped with internal bypass relays initiated by its microprocessor control (on units 31-310
amps).

Using the soft stop, the RVS-DX slowly reduces the motor voltage, thus softly stopping a high
friction load. In applications where the inertia of a load would cause the motor to “free wheel”; the
soft stop will not stop the motor any faster than the coast to stop.

Starter Selection

Select the RVS-DX soft starter according to the motor’s Full Load Amps. Also consider the
following information:

Maximum starts per hour:

4 starts per hour at maximum ratings up to 10 starts/hour for
lightly loaded applications.

NOTE:

For very frequent starts (inching applications) the inching current should be considered
the FLA.

Supply Voltage (Line to Line): +10%–15%

Standard Supply Voltage:

220–240 volts
460–500 volts
575–600 volts

Special Order Voltage:

380–440 volts

NOTE:

All RVS-DX units are suitable for 50/60 Hz.

Control Voltage:

110-120 volts (+10% -15%); 50/60 Hz (standard)
220-240 volts (+10% -15%); 50/60 Hz

Ambient Temp. I start

Acc Time

40°C

300% In

30 Sec.

350% In

20 Sec.

400% In

5 Sec.

Advertising