4. Concealed Duct Type (U Type)

4-5. Increasing the Fan Speed

Fig. 4-1

Inter-unit control wiring

Power supply outlet

HT : Using the booster cable

H : At shipment

177

Air Flow (CFM)

Air Flow (CFM)

Air Flow (CFM)

Air Flow (CFM)

353

Limit line

Limit line

HT

H

M

L

706

353

HT

H

L

M

1059

706

HT

L

M

H

530

353

HT

M

L

H

18 Type

7, 12 Type

Indoor Fan Performance

24 Type

36 Type

NOTE

Exter

nal Static Pressure

0.40

0.20

0.60

(in.WG)

Exter

nal Static Pressure

(1) Remove 4 screws on the electrical component box and
remove the cover plate.

(2) Disconnect the fan motor sockets in the box.

(3) Take out the booster cable (sockets at both ends)
clamped in the box.

(4) Securely connect the booster cable sockets between
the disconnected fan motor sockets in step 2 as shown
in Fig. 4-2.

(5) Place the cable neatly in the box and reinstall the cover
plate.

Fig. 4-2

Booster cable

Electrical component box

(At shipment)

(Booster cable installed)

Fan motor socket

Fan
motor

How to read the diagram

If external static pressure is too great (due to long extension of ducts,
for example), the air flow volume may drop too low at each air outlet.
This problem may be solved by increasing the fan speed using the
following procedure:

Booster cable

0

(in.WG)

0.40

0.20

0.60

0

Limit line

Limit line

Exter

nal Static Pressure

0.40

0.20

0.60

0

(in.WG)

(in.WG)

Exter

nal Static Pressure

0.40

0.20

0.60

0

Limit line

Limit line

Limit line

Limit line

The vertical axis is the external static pressure (in.WG)
while the horizontal axis represents the air flow (CFM).
The characteristic curves for "HT," "H," "M" and gL h fan
speed control are shown. The nameplate values are
shown based on the gH h air flow. For the 24 type, the air
flow is 635 CFM, while the external static pressure is
0.20 in.WG at gH h position. If external static pressure is
too great (due to long extension of ducts, for example),
the air flow volume may drop too low at each air outlet.
This problem may be solved by increasing the fan speed
as explained above.