Electrical wiring – Sanyo CHX03652 User Manual

Page 208

Advertising
background image

5-20

Test Run and Others

1

2

3

4

5

6

7

8

Outdoor unit

Outdoor unit

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

more than 3.3 ft.

more than 3.3 ft.

Branch
point

16 or fewer

Indoor unit

Indoor unit

Indoor unit

Indoor unit

less than 3.3 ft.

Indoor unit

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Outdoor unit

Indoor unit

NO

NO

Branch point

(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the

short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor
units except any one of the outdoor units.
(When shipping: In shorted condition.)

Otherwise the communication of S-net link system is not performed. For a system without link (no
connection wiring between outdoor units), do not remove the short plug.

(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 5-13)

Outdoor unit

Outdoor unit

Outdoor unit

Prohibited

Prohibited

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Fig. 5-13

Fig. 5-14

Fig. 5-15

CAUTION

(3) Do not install inter-unit control wiring such as star

branch wiring. Star branch wiring causes mis-address

setting.

(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.

(Branches less than 3.3 ft. are not included in the total branch number.) (Fig. 5-15)

3. Electrical Wiring