System design – Sanyo CHX03652 User Manual

Page 26

Advertising
background image

2-18

Design of Mini ECO-i SYSTEM

1

2

3

4

5

6

7

8

Outdoor unit

Room 1

(indoor unit 1)

Room 2

(indoor unit 2)

Room 3

(indoor unit 3)

Room 4

(indoor unit 4)

Selected model

CHX06052

Maximum load
(cooling/heating) (BTU/h)

(cooling/heating) (BTU/h)

Rated capacity
(cooling/heating) (BTU/h)

(5) Corrected capacity

(cooling/heating) (BTU/h)

(7) Actual capacity

(cooling/heating) (BTU/h)

Total corrected capacity of all indoor units (cooling/heating) = 36,900 / 44,500

Ruc = 36,900 / 45,900 = 0.804

< 1 Ruh = 44,500 / 47,300 = 0.941 < 1

•For both cooling and heating in all rooms, actual capacity is now greater than or equal to the maximum

load. Selection is completed.

Indoor unit changes

Type 1252

Type 0752

Type 1252

Type 0752

12,000 / 14,000

52,900 / 60,000

10,000 / 12,000 7,000 / 8,400

7,000 / 8,400

7,000 / 8,400

7,500 / 8,500

7,500 / 8,500

12,000 / 14,000

52,900 / 60,000

1.00 / 1.00

1.020 / 0.937

0.920 / 0.980

0.851 / 0.946

1.000 / 1.000

1.062 / 1.020

1.012 / 1.004

1.037 / 1.012

0.920 / 0.980

0.920 / 0.980

0.920 / 0.980

7,500 / 8,500

7,500 / 8,500

12,000 / 14,000

12,000 / 14,000

45,900 / 47,300

11,700 / 14,000 7,200 / 8,400

7,000 / 8,400 11,000 / 13,700

11,700 / 14,000 7,200 / 8,400

7,000 / 8,400 11,000 / 13,700

Outdoor unit

Room 1

(indoor unit 1)

Room 2

(indoor unit 2)

Room 3

(indoor unit 3)

Room 4

(indoor unit 4)

Rated capacity

(1) Model

(2) Temp. condition

(3) Tubing length,

elevation difference

Correction coefficient

*1: This varies depending on the values of (2) and (2)

× (Distribution ratio in (3)).

*2: Corrected outdoor unit capacity = Rated outdoor unit capacity

Ч (1) Ч (2) Ч (3) Ч (4)

11,700 / 14,000

11,700 / 14,000

45,900 / 47,300

0.977 / 1.000

0.954 / 0.992

0.992 / 0.984

0.920 / 0.980

0.977 / 1.000

0.954 / 0.992

1.00 / 1.00

0.992 / 0.984

0.920 / 0.980

7,200 / 8,400

7,000 / 8,400 11,000 / 13,700

7,200 / 8,400

7,000 / 8,400 11,000 / 13,700

(4) Frosting • defrosting

Result of (2)

× (3)

Correction coefficient
applied to indoor unit *1

(5) Corrected capacity (BTU/h) *2

(6) Correction coefficient

for corrected capacity
ratio

(7) Actual capacity (BTU/h)

— / 0.890

(2) Calculate the final selection results according to the capacity calculation procedure.

[From calculation of the correction coefficient to calculation of actual capacity]

(Cooling/heating)

The indoor unit in room 4, where the corrected indoor unit capacity is less than the maximum load, is
increased by one rank.

The actual capacity is calculated as shown below.

Cooling: Ruc = (11,700 + 7,200 + 7,000 + 11,000) / 45,900 = 0.804 < 1

Therefore,

Actual cooling capacity of each indoor unit = Corrected cooling capacity of each indoor unit

(In other words, the correction coefficient [6] for the corrected capacity ratio is 1.)

Heating: Ruh = (14,000 + 8,400 + 8,400 + 13,700) / 47,300 = 0.941 < 1

Therefore,

Actual heating capacity of each indoor unit = Corrected heating capacity of each indoor unit

(In other words, the correction coefficient (6) for the corrected capacity ratio is 1.)

2. System Design