System design – Sanyo CHX03652 User Manual

Page 28

Advertising
background image

2-20

Design of Mini ECO-i SYSTEM

1

2

3

4

5

6

7

8

Checking of limit density

Density limit is determined on the basis of the size

of a room using an indoor unit of minimum capacity.

For instance, when an indoor unit is used in a room

(floor area 80 ft

2

× ceiling height 8.8 ft. = room volume

704 ft.

3

), the graph at right shows that the minimum

room volume should be 497 ft.

3

(floor area 56 ft.

2

) for

refrigerant of 147 oz. Accordingly, openings such as

louvers are required for this room.

<Determination by calculation>

Overall refrigerant charge amount for the air conditioner: oz

(Minimum room volume for indoor unit: ft.

3

)

=

147 (oz) + 123 (oz)

= 0.38 (oz/ft.

3

)

≥≥ 0.3 (oz/ft

3

)

704 (ft

3

)

Therefore, openings such as louvers are required for

this room.

Obtain charge amount for each tubing size

Note that the charge amounts per 3.3 ft. are different for each liquid tubing size.

ш3/8" (ш9.52)

→ LA + LB + LC + LD

: 212 ft.

× 0.602 oz/ft. = 127 oz

ш1/4" (ш6.35)

→ 1 + 2 + 3 + 4 + 5 : 75 ft. × 0.279 oz/ft. = 20 oz

Total

147

oz

Additional refrigerant charge amount is 147 oz.

Be sure to check the limit density

for the room in which the indoor

unit is installed.

CAUTION

Example of each tubing length

Main tubing Distribution joint tubing

LA = 131 ft.

Indoor side

LB = 16 ft.

1 = 16 ft.

4 = 20 ft.

LC = 16 ft.

2 = 16 ft.

5 = 16 ft.

LD = 49 ft.

3 = 7 ft.

LN

L1
L2

LC

LB

LA

Main tube of unit

1st branch

model 0752

model 0952

model 1252

model 1852

model 1852

Unit distribution tube

1

2

3

n–1

n

Example:

57

114

170

227

284

341

398

454

0

500

1000

1500

2000

2500

3000

3500

4000

400

200

600

800 1000 1200

Total amount of refrigerant

Min.

indoor v

olume

Min.

indoor floor area

(when the ceiling is 8.8 ft.

high)

ft.

3

ft.

2

oz

Range above
the density limit of
0.3 oz/ft.

3

(countermeasures
needed)

Range below
the density limit of
0.3 oz/ft.

3

(countermeasures
not needed)

0 0

2. System Design