4-59

Mini ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

6. Ceiling-Mounted Type (T Type)

Unit specifications (C)

MODEL No.

Indoor Unit

THX2452

POWER SOURCE

208 - 230 V / 1ø / 60 Hz

PERFORMANCE

Cooling

Heating

Capacity

BTU / h

25,000

27,000

kW

7.3

8.0

Air circulation (Hi / Me / Lo)

CFM

650 / 530 / 495

Moisture removal (High)

Pints / h

6.34

ELECTRICAL RATINGS

Voltage rating

V

208

230

208

230

Available voltage range

V

187 - 253

187 - 253

Running amperes

A

0.34

0.31

0.34

0.36

Power input

W

38

37

40

40

Power factor

%

54

52

57

48

Max. starting amperes

A

2

2

2

2

FEATURES

Controls

Microprocessor

Fan speeds

3 and Automatic control

Air filter

Washable, easy access, long life (2,500hr)

Refrigerant control

Electronic expansion valve

Operation sound (Hi / Me / Lo)

dB-A

38 / 36 / 33

Refrigerant tubing connections

Flare type

Refrigerant tube di-

ameter

Liquid tube

in. (mm)

3 / 8 (9.52)

Gas tube

in. (mm)

5 / 8 (15.88)

Drain connection

25 A, OD 1-1 / 32”

Remote controller

Optional (RCS-TM80BG, RCS-TRP80AAB.WL)

Refrigerant tubing kit / Accessories

Optional / –

Color (Approximate value)

Munsell 10Y9.0 / 0.4, RAL 9010-GL

DIMENSIONS & WEIGHT

Unit dimensions

Package dimensions

Unit dimensions

Height

in. (mm)

8-9 / 32 (210)

11-1 / 32 (280)

Width

in. (mm)

46-15 / 32 (1180)

49-13 / 32 (1255)

Depth

in. (mm)

26-25 / 32 (680)

30-23 / 32 (780)

Net weight

lbs. (kg)

55 (25)

Shipping weight

lbs. (kg)

62 (28)

Shipping volume

ft

3

(m

3

)

9.7 (0.274)

Rated conditions

Colling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB

chap_04-06-1.indd 59

2007/07/23 13:35:34

Advertising