Design of Mini ECO-i SYSTEM

2-11. System Example

(1) Below are the tables created using the “Sanyo PAC System Diagram Software.”

Details of the calculations are shown in (2).

Selection conditions
Assumes that installation is in a 60 Hz region.

Outdoor unit

Room 1

(indoor unit 1)

Room 2

(indoor unit 2)

Room 3

(indoor unit 3)

Room 4

(indoor unit 4)

Air condition
(DB/WB)

Cooling

Max. load (BTU/h)

Air condition
(DB/WB)

Heating

Max. load (BTU/h)

Actual tubing length

Preliminary selection

Outdoor unit

Room 1

(indoor unit 1)

Room 2

(indoor unit 2)

Room 3

(indoor unit 3)

Room 4

(indoor unit 4)

Selected model

CHX03652

Type 1252

Type 0752

Type 0752

Type 0752

Type 1252

Type 0752

Type 0752

Type 0752

Load (cooling/heating) (BTU/h)

Rated capacity
(cooling/heating) (BTU/h)

(5) Corrected capacity

(cooling/heating) (BTU/h)

(7) Actual capacity

(cooling/heating) (BTU/h)

Total corrected capacity of indoor units (cooling/heating) = 32,800 / 39,100
Ruc = 32,800 / 33,200 = 0.988

< 1 Ruh = 39,100 / 33,700 = 1,160 > 1

91.0 / 72.0

38,200 / 42,700

52,900 / 60,000

33,200 / 33,700

45,900 / 47,300

11,700 / 14,000

11,700 / 14,000

11,700 / 14,000

11,700 / 12,200 7,200 / 7,400

7,000 / 7,300

7,200 / 8,400

7,200 / 8,400

7,200 / 8,400

7,000 / 8,400

7,000 / 8,400

7,000 / 8,400

6,900 / 8,300

6,900 / 8,300

6,900 / 8,300

6,900 / 7,300

37.0 / 35.0

69.0 / 55.0

69.0 / 55.0

69.0 / 55.0

69.0 / 55.0

78.0 / 64.0

12,000 / 14,000

12,000 / 14,000

7,500 / 8,500

7,500 / 8,500

7,500 / 8,500

7,500 / 8,500

7,500 / 8,500

7,500 / 8,500

78.0 / 64.0

78.0 / 64.0

78.0 / 64.0

10,000

7,000

7,000

7,000

10,000 / 12,000 7,000 / 8,400

7,000 / 8,400

7,000 / 8,400

10,000 / 12,000 7,000 / 8,400

7,000 / 8,400

7,000 / 8,400

8,400

8,400

8,400

12,000

246 ft.

295 ft.

197 ft.

236 ft.

276 ft.

295 ft.

246 ft.

230 ft.

197 ft.

164 ft.

Outdoor unit

Room 1

(indoor unit 1)

Room 2

(indoor unit 2)

Room 3

(indoor unit 3)

Room 4

(indoor unit 4)

Selected model

CHX06052

Maximum load
(cooling/heating) (BTU/h)

Rated capacity
(cooling/heating) (BTU/h)

(5) Corrected capacity

(cooling/heating) (BTU/h)

(7) Actual capacity

(cooling/heating) (BTU/h)

Total corrected capacity of all indoor units (cooling/heating) = 32,800 / 39,100

Ruc = 32,800 / 45,900 = 0.715

< 1 Ruh = 39,100 / 47,300 = 0.827 < 1

Outdoor unit changes

Selected model

CHX03652

Type 1252

Type 0752

Type 0752

Type 0752

During heating, the corrected outdoor unit capacity is less than the total corrected capacity of all indoor units
in the system. As a result, the actual capacity of each indoor unit is less than the maximum load. Therefore
the outdoor unit is increased by one rank.

Equivalent length (with
consideration for curves, etc.)

Indoor

unit 1

33 ft.

33 ft.

Indoor

unit 2

33 ft.

Indoor

unit 3

33 ft.

Indoor

unit 4

131 ft.

33 ft.

49 ft.

Outdoor

unit

Elevation
difference: 33 ft.