Design of Mini ECO-i SYSTEM

3-1. Indoor Unit

AVOID:

areas where leakage of flammable gas may be

expected.

places where large amounts of oil mist exist.

direct sunlight.

locations near heat sources which may affect the

performance of the unit.

locations where external air may enter the room

directly. This may cause “sweating” on the air
discharge ports, causing them to spray or drip.

locations where the remote controller will be splashed

with water or affected by dampness or humidity.

installing the remote controller behind curtains or

furniture.

locations where high-frequency emissions are

generated.

DO:

select an appropriate position from which every corner

of the room can be uniformly cooled.

select a location where the ceiling is strong enough to

support the weight of the unit.

select a location where tubing and drain pipe have the

shortest run to the outdoor unit.

allow room for operation and maintenance as well as

unrestricted air flow around the unit.

install the unit within the maximum elevation difference

above or below the outdoor unit and within a total
tubing length (L) from the outdoor unit as detailed in
Table 2-10.

allow room for mounting the remote controller about

3 ft. off the floor, in an area that is not in direct sunlight
nor in the flow of cool air from the indoor unit.

NOTE

Air delivery will be degraded if the distance from the floor

to the ceiling is greater than 10 ft.

Concealed Duct (High-Static Pressure) Type

3 ft.

3 ft.

3 ft.

3 ft.

3 ft.

4-Way Air Discharge Semi-Concealed Type

Wall-Mounted Type

min. 6 in.

Front View

min.
6 in.

min.
6 in.

Ceiling-Mounted Type

Side view

min. 10 in.

The rear of the indoor unit can be installed flush
against the wall.

min. 2 ft.

Air intake

Air
discharge

min. 10 in.

Ceiling

Wall

Front view

Max. 10 in.

Obstacle

NOTE

Fig. 2-1

Fig. 2-2

min. 2 in.

min. 2 in.

min.

3 ft.

Air
intake

Air
discharge

Obstacle

Ceiling

Wall

Wall

Side view

1-Way Air Discharge Semi-Concealed Type

Fig. 2-3

Fig. 2-4

3. Installation Instructions