Electrical wiring – Sanyo CHX03652 User Manual

Page 40

Advertising
background image

2-32

Design of Mini ECO-i SYSTEM

1

2

3

4

5

6

7

8

Control wiring

(C) Inter-unit (between outdoor and

indoor units) control wiring

(D) Remote control wiring

(E) Control wiring for group control

AWG #18 (0.75 mm

2

)

AWG #18 (0.75 mm

2

)

AWG #18 (0.75 mm

2

)

Use shielded wiring*

Use shielded wiring

Use shielded wiring

Max. 3,280 ft.

Max. 1,640 ft.

Max. 1,640 ft. (Total)

4-1. General Precautions on Wiring

(1) Before wiring, confirm the rated voltage of the unit

as shown on its nameplate, then carry out the

wiring closely following the wiring diagram.

(2) Provide a power outlet to be used exclusively for

each unit, and a power supply disconnect and

circuit breaker for overcurrent protection should be

provided in the exclusive line.

(3) To prevent possible hazards from insulation failure,

the unit must be grounded.

(4) Each wiring connection must be done in

accordance with the wiring system diagram.

Wrong wiring may cause the unit to misoperate or

become damaged.

(5) Do not allow wiring to touch the refrigerant tubing,

compressor, or any moving parts of the fan.

(6) Unauthorized changes in the internal wiring can be

very dangerous. The manufacturer will accept no

responsibility for any damage or misoperation that

occurs as a result of such unauthorized changes.

(7) Regulations on wire diameters differ from locality

to locality. For field wiring rules, please refer

to your LOCAL ELECTRICAL CODES before

beginning.

You must ensure that installation complies with all

relevant rules and regulations.

(8) To prevent malfunction of the air conditioner

caused by electrical noise, care must be taken

when wiring as follows:

The remote control wiring and the inter-unit control

wiring should be wired apart from the inter-unit

power wiring.

Use shielded wires for inter-unit control wiring

between units and ground the shield on both sides.

(9) If the power supply cord of this appliance is

damaged, it must be replaced by a repair shop

appointed by the manufacturer, because special

purpose tools are required.

4-2. Recommended Wire Length and Wire Diameter for Power Supply System

Outdoor unit

CHX03652

30 A

CHX06052

50 A

Time delay fuse or

circuit capacity

Indoor unit

Time delay fuse or

circuit capacity

K

A, X, T, U

Type

Type

15 A

For field wiring rules, please refer to
your LOCAL ELECTRICAL CODES

For field wiring rules, please refer to
your LOCAL ELECTRICAL CODES

(A) Power supply wiring

(B) Power supply wiring

15 A

15 A

D

NOTE

* With ring-type wire terminal.

4. Electrical Wiring

Advertising
This manual is related to the following products: