Transformer, Step 2 120 vac to transformer – State Industries Utra-Force STC-077 User Manual

Page 20

Advertising
background image

S U F S E R V I C E H A N D B O O K

T R O U B L E S H O O T I N G

State Water Heaters

Technical Training Department

Ashland City, Tennessee © 2004

19

STC-077

TRANSFORMER

STEP 2: CHECK FOR 120 VAC TO TRANSFORMER FROM PIN 1 AND 2 ON CONTROL
BOARD CN4 TERMINAL.
Condition:

• Disconnect CN4 plug from control board.
• On/Off switch is on.

Check for 120 VAC between pin 1 and 2 at CN4 on the control board as illustrated above. Perform
this test with the CN4 plug disconnected and the On/Off switch turned on.

STEP 2

120 VAC TO TRANSFORMER

IF…

THEN

120 VAC is not present

check CN1 plug connection
replace control board if Step 1 has been performed and results were successful.

120 VAC is present

reconnect CN4 plug to control board, continue to Step 3.