Installation, Clearances, Gas requirements – State Industries Utra-Force STC-077 User Manual

Page 4

Advertising
background image

S U F S E R V I C E H A N D B O O K

I N S T A L L A T I O N

State Water Heaters

Technical Training Department

Ashland City, Tennessee © 2004

3

STC-077

INSTALLATION

CLEARANCES

This portion of the handbook will review
often overlooked installation require-
ments. The installation manual covers
these items in detail. SUF water heaters
are approved for installation on com-
bustible flooring. The minimum clear-
ance to combustibles or non-
combustibles is 0 inches from the sides
and rear, 0 inches from vent piping, and
1.5 inches from the top cover. A 24 inch
clearance for all serviceable parts is
recommended. Clearances may vary
between SUF models. See installation
manual or the label on the heater for
your specific model.

GAS REQUIREMENTS

N O T E :

Pressure without capacity will result in lockout. Follow the piping guidelines in the

installation manual. The supply gas pressure is normally measured at the dirt leg or at the inlet gas
pressure tap on the gas valve. This reading must be measured with ‘flowing’ gas.

The manifold gas pressure is measured at the manifold pressure tap on the gas valve when the
gas is flowing. The gas valves used on all SUF water heaters are 24 VAC combination step open-
ing gas valves. They incorporate the main valve and pressure regulator into one body.

GAS SUPPLY SPECIFICATIONS

SUF 240

SUF 150 & 199

SUF 150 & 199

NATURAL GAS

NATURAL GAS

PROPANE GAS

Max. Gas Supply Pressure Inches W.C.

12.0 (3 kPa)

12.0 (3 kPa)

14.0 (3.45 kPa)

Nominal Gas Supply Pressure Inches W.C.

7.0 (1.75 kPa)

7.0 (1.75 kPa)

11.0 (2.74 kPa)

Minimal Gas Supply Pressure Inches W.C.

5.5 (1.37 kPa)

4.5 (1.12 kPa)

11.0 (2.74 kPa)

Manifold Pressure Inches W.C.

4.0 (1 kPa)

3.5 (0.8 kPa)

10.0 (2.5 kPa)

REGULATED GAS SUPPLY LINE

MAIN GAS
SHUTOFF VALVE

DIRT LEG TEE

PIPE CAP

PRESSURE REGULATOR
ADJUSTMENT
(COVER SCREW)

INLET PRESSURE
TAP

GAS INLET

GAS VALVE ON/OFF

TH & TR TERMINALS
(MAIN VALVE)

MANIFOLD
PRESSURE TAP

GAS OUTLET

Advertising