5 temperature, 6 battery, Temperature – Siemens Plant Central Clock TC100 User Manual

Page 84: Battery

Advertising
background image

Parameter assignment

9-8



©

Siemens AG 2010 All Rights Reserved

SICLOCK

®

TC100 Operating Instructions

9.3.5

Temperature

You activate the monitoring of the module temperature with the parameter entry
/Environment/Extended/Temperature/Monitoring (0.24.01).

You can set the following values:

Alarm

Warning

No monitoring

The current module temperature is shown in the parameter entry
/Environment/Status/Temperature (0.24.02).

9.3.6

Battery

You can switch the battery off for storage with the parameter entry
/Environment/Extended/Battery/Switch Off (0.25.01), and so substantially
lengthen the life of the battery in storage.

After a minimum operating period of 30 minutes after Power Up, SICLOCK

TC100 checks once whether the battery is switched off. If necessary, the battery

is then switched on automatically, and a message is output.

See Battery (Chapter 11.1).

Notice

If the supply voltage is switched off while the battery is switched off, the SICLOCK
TC100 loses the hardware time and the archives.

This command may only be executed by qualified personnel.

Advertising