Siemens Plant Central Clock TC100 User Manual

Page 99

Advertising
background image

Technical data

13-9



©

Siemens AG 2010 All Rights Reserved

SICLOCK

®

TC100 Operating Instructions

Battery

Service life in operation

> 12 years

Service life when switched off
during storage

> 12 years

Service life when switched on
during storage

< 6 years, see Battery (Chapter 11.1)

Electromagnetic compatibility (EMC)

Radiated interference

EN 55022 class A, FCC class A

Interference immunity

EN 55024

Environmental characteristics

In operation

EN 60721-3-3 (stationary use in weather-proof locations) class 3K3,

During storage/transport

EN 60721-3-2 class 2K4

Climatic conditions

Temperature in operation

0°C to 55°C

Temperature during
storage/transport

-40°C to +70°C

Temperature gradient

10°C/h max. in operation, 20°C/h in storage, no condensation

Relative humidity
- Operation
- Storage / transport

Tested according to IEC 60068-2-78, IEC 60068-2-30
10% to 95% at 25°C (no condensation)
10% to 95% at 25°C (no condensation)

Atmospheric pressure

1080 to 795 hPa (corresponds to an elevation of -1000 to 2000 m)

Mech. environmental conditions

During operation

EN 60721-3-3, class 3M3

During storage / transport

EN 60721-3-2, class 2M2

Interfaces (see also Connection (Chapter 6))

Ethernet connection

1x Ethernet port, 10/100 Mbit/s, autonegotiation

8-pin terminal strip (see also Terminal assignment (Chapter 15.1))

Radio clock input
(short-circuit proof)

Rated current 20 mA to 40 mA, supply voltage 48 V for connecting to
SICLOCK GPS1000, SICLOCK GPSDEC or SICLOCK DCFRS
The radio clock input is galvanically separated from the rest of the
electronics.

1 relay output NC contact for
WARNING signal

0.06 A, 48 VDC max.

1 relay output NC contact for
ALARM signal

0.06 A, 48 VDC max.

Table 13-1

SICLOCK TC100, technical data

Advertising