NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Blocking

Support Straps

(Plumber's tape)

8 feet (2.4 m)

Maximum

1 inch (25.4

mm) minimum

clearance to

combustibles

F. Change vent direction to horizontal / inclined

run - At transition from or to a horizontal / in-

clined run, install the SV4.5E45 and SV4.5E90

elbows in the same manner as the straight vent

sections. The elbows feature a twist section to

allow them to be routed about the center axis

of their initial collar section to align with the

required direction of the next vent run element.

Twist elbow sections in a clockwise direction

only so as to avoid the possibility of unlocking

any of the previously connected vent sections.

See Figure 24.

7-5/8”

(194 mm)

4-13/16

(122 mm)

Swivel Joint

(360° swivel)

SV4.5E45

45° Elbow)

Swivel Joint

(360° swivel)

SV4.5E90

90° Elbow)

(206 mm)

8-1/8"

Figure 24

v

SV4.5VF

Firestop / spacer

u

SV4.5SU

Support Strap

8 ft. (2.4 M)

Maximum

u

SV4.5SP

Support Plate

Ceiling Framing

u

Secured

to Vent with

Appropriate

Fasteners

1” (25.4 mm)

Minimum

Clearance to

Combustibles

v

When using

secure Flex, use

Firestop/Spacer

SF4.5VF

SV4.5FA or

SV4.5FB Flashing

and SV4.5SC

Storm Collar

SV4.5CGV-1

Termination

Figure 23

16

Figure 22

Another method, where the vent is not adjacent

to a wall, is illustrated in Figure 23. Here,

support straps (96K93) and support plates

(96K92) can be used to support the weight

of the vent.

E. Support the vertical vent run sections -

Note - Proper venting support is very important.

The weight of the vent must not be supported

by the fireplace in any degree.

Support the vertical portion of the venting

system every 8 feet (2.4 m) above the fireplace

vent outlet.

One method of support is by utilizing field pro-

vided support straps (conventional plumber's

tape). Secure the plumber's tape to the framing

members with nails or screws. Loop the tape

around the vent, securing the ends of the tape to

the framing. If desired, sheet metal screws #6

x 1/2" length may be used to secure the support

straps to the vent pipe. See Figure 22.

Note: Trim Thimble/

Extension To Desired Length

And Pitch At The Roof Line

14" Min.

Pitched Roof

Pitched Roof

Bow Roof

14" Min.

Outer Pipe Of

Chimney

Outer Pipe Of

Chimney

Outer Pipe Of

Chimney

14" Min.

Firestop

Thimble

Extension

13"

Firestop

Thimble

Firestop

Thimble

Thimble

SV-FSTFE

Figure 21

G. Continue installation of horizontal / inclined

sections - Continue with the installation of the

straight vent sections in horizontal / inclined run

as described in Step C. Install support straps

every 5 feet (1.52 m) along horizontal / inclined

vent runs using conventional plumber’s tape.

See Page 20, Figure 33. It is very important

that the horizontal / inclined run be maintained

in a straight (no dips) and recommended to

be in a slightly elevated plane, in a direction

away from the fireplace of 1/4" rise per foot (20

mm per meter) which is ideal, though rise per

foot run ratios that are smaller are acceptable

all the way down to at or near level.