Superior MILLIVOLT SDVST-N-B User Manual

Page 20

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

20

HORIZONTAL (OUTSIDE WALL)

TERMINATION SYSTEM

See Figure 33, and Figures 36 to 41 (Pages

22 to 24) and their associated Horizontal Vent

Table which illustrates the horizontal venting

configurations that are allowed to be used with

these appliances. Secure Vent pipe applications

are shown in these figures; Secure Flex pipe may

also be used (see Page 25). A Horizontal Vent

Table summarizes each system’s minimum and

maximum vertical and horizontal length values

that can be used to design and install the vent

components in a variety of applications.
Both of these horizontal vent systems terminate

through an outside wall. Building Codes limit or

prohibit terminating in specific areas. Refer to

Figure 5 on Page 7 for location guidelines.
Secure Vent SV4.5 direct-vent system compo-

nents are unitized concentric pipe components

featuring positive twist lock connection, (refer

to Figure 19 on Page 15). All of the appli-

ances covered in this document are fitted with

collars having locking inclined channels. The

dimpled end of the vent components fit over

the appliance collar to create the positive twist

lock connection.

A. Plan the vent run -

Analyze the vent routing and determine the

types and quantities of sections required

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572

mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm)

net section lengths are available. It is recom-

mended that you plan the vent lengths so that

a section joint does not occur within the space

defined by ceiling joists, roof rafters or wall studs.

Make allowances for elbows as indicated in Figure

24 on Page 16.
Maintain a minimum 1" (25 mm) clearance to

combustibles on the vertical sections. Clear-

ances for the horizontal runs are; 3" (76 mm)

on top, 1" (25 mm) on sides, and 1" (25 mm)

at the bottom.

Figure 33 -

TYPICAL HORIZONTAL VENT INSTALLATION

See Figures 22 and 23 on

Page 16 for vertical vent

section support.

Horizontal / Inclined Run

Support

Brackets

Building

Support

Framing

SV4.5E90

Elbow

Ceiling

Firestop / Spacer

SV4.5VF

When Using Secure Flex,

Use Firestop / Spacer SF4.5VF

Fireplace

SV4.5L6/12/24/36/48

Vent Sections

Vertical

Rise

Support Bracket Spacing

Every 5 ft (1.52 m)

Exterior

Wall

TYPICAL HORIZONTAL VENT INSTALLATION

SV4.5HT-2

Termination

Shown

SV4.5HT-2

Termination

Shown

B. Frame exterior wall opening -

Locate the center of the vent outlet on the exte-

rior wall according to the dimensions shown in

Figures 11 and 12 on Pages 10 and 11.
Cut and/or frame an opening, 10-1/2" x 12-1/8"

(267 mm x 308 mm) inside dimensions, about

this center.

C. Frame ceiling opening - If the vertical route

is to penetrate a ceiling, use plumb line to locate

the center above the appliance. Cut and/or frame

an opening, 10-1/2" x 10-1/2" (267 mm x 267

mm) inside dimensions, about this center (refer

to Figure 18 on Page 15).

D. Attach vent components to appliance - To

attach a vent component to the appliance collar,

align the dimpled end over the collar, adjust-

ing the radial alignment until the four locking

dimples are aligned with the inlets of the four

incline channels on the collar (refer to Figure

19 on Page 15).

Push the vent component against the collar

until it fully engages, then twist the component

clockwise, running the dimples down and along

the incline channels until they seat at the end of

the channels. The unitized design of the Secure

Vent components will engage and seal both the

inner and outer pipe elements with the same

procedure. Sealant and securing screws are

not required.

E. Attach vent components to each other

- Other vent sections may be added to the

previously installed section in accordance with

the requirements of the vent tables.

To add another vent component to a length

of vent run, align the dimpled end of the

component over the inclined channel end of

the previously installed section, adjusting the

radial alignment until the four locking dimples

are aligned with the inlets of the four incline

channels of the previous section.

Push the vent component against the previous

section until it fully engages, then twist the

component clockwise running the dimples

down and along the incline channels until they

seat at the end of the channels. This seating

position is indicated by the alignment of the

arrow and dimple as shown in Figure 19 on

Page 15.

F. Install firestop / spacer at ceiling -

Install a Secure Vent SV4.5VF firestop/spacer

at the bottom side of the ceiling to the ceiling

joists. Route the vent sections through the

framed opening and secure the firestop/spacer

with appropriate fasteners at each corner.

If there is living space above the ceiling level,

the firestop/ spacer must be installed on the

bottom side of the ceiling. If attic space is

above the ceiling, the firestop/ spacer must

be installed on the top side of the joist. Route

the vent sections through the framed opening

and secure the firestop / spacer with 8d nails

or other appropriate fasteners at each corner.

Remember to maintain 1" (25 mm) clearance

to combustibles, framing members, and attic

or ceiling insulation when running vertical

chimney sections. Attic insulation shield

(H3907) may be used to obtain the required

clearances indicated here. See installation

accessories tables on Pages 34 through 36.

G. Support the vertical run sections -

See Step E on Page 16.

H. Change vent direction - At transition from

or to a horizontal / inclined run, install the

SV4.5E45 and SV4.5E90 elbows in the same

manner as the straight vent sections. The

elbows feature a twist section to allow them to

be routed about the center axis of their initial

collar section to align with the required direc-

tion of the next vent run element. Twist elbow

sections in a clockwise direction only so as

to avoid the possibility of unlocking any of

the previously connected vent sections. See

Figure 24 on Page 16.

I. Continue installation of horizontal / inclined

sections - Continue with the installation of the

straight vent sections in horizontal / inclined run

as described in Step E. Install support straps

every 5 ft. (1.52 m) along horizontal / inclined

vent runs using conventional plumber’s tape.

See Figure 33. It is very important that the

horizontal / inclined run be maintained in a

straight (no dips) and recommended to be in

a slightly elevated plane, in a direction away

from the fireplace of 1/4" rise per foot (20 mm

per meter) which is ideal, though rise per foot

run ratios that are smaller are acceptable all the

way down to at or near level. Use a carpenter’s

level to measure from a constant surface and

adjust the support straps as necessary.

u

u

Advertising
This manual is related to the following products: