NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

21

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all sides

for all vertical runs; and 3" (76 mm) at the

top, 1" (25 mm) at sides, and 1" (25 mm) at

the bottom for all horizontal / inclined runs.

J. Assemble vent run to exterior wall - If not

previously measured, locate the center of the

vent at the exterior wall. Prepare an opening

as described in Step B. Assemble the vent

system to point where the terminus of the last

section is located relative to the exterior surface

to which the termination is to be attached as

shown in Figure 34.

If the terminus of the last section is not within

this distance, use the telescopic vent section

SV4.5LA, as the last vent section. For wall

thicknesses greater than that shown in Figure

35, refer to Table 8 on Page 22. This Table lists

the additional venting components needed (in

addition to the termination and adapter) for a

particular range of wall thicknesses.

K. Attach termination adapter - Attach the

adapter (SV4.5RCH - provided with the termi-

nation) to the vent section or telescoping vent

section), elbow or appliance collar as shown in

Figures 34 and 35 in the same manner as any

SV4.5 vent component (refer to Step E).

L. Install Firestop / Spacer at exterior wall

- When using the square termination, install

SV4.5HF (Secure Vent), SF4.5HF (Secure Flex)

Firestop / Spacer over the opening at the exterior

side of the framing, long side up, with the 3 inch

spacer clearance at the top as shown in Figure

34, and nail into place.

(The Firestop/Spacer may also be installed over

the opening at the interior side of framing).

M. Install the Square Termination (SV4.5HT-2)

For the last step, from outside the exterior wall,

slide the collars of the termination onto the

adapter until the termination seats against the

exterior wall surface to which it will be attached.

Orient the housing of the termination with the

arrow pointed upwards. Secure the termination

to the exterior wall. The horizontal termination

must not be recessed into the exterior wall

or siding by more than the 1-1/4" (32 mm) as

shown in Figure 35.

IMPORTANT: The vent termination is hot

while in operation and for a period of time

following the use of the fireplace. Young

children should be carefully supervised

when they are in the same area as a hot

termination. To prevent contact with hot

surfaces, we recommend the use of a

Termination Guard. See Page 34. This

can be purchased at your local dealer.

See Figures 11 and 12 on Pages 10 and
11
for Min. Distance to Base of Appliance.

SV4.5 HT-2

Termination

SV4.5 HT-2

Termination

SV4.5 HT-2

Termination

Horizontal terminations have been designed to perform in a wide range of weather condi-

tions. Our terminations meet or exceed industry standards.

When selecting the locations of your horizontal terminations, do not place the termina-

tion where water from eaves and adjoining rooflines may create a heavy flow of cascad-

ing water onto the termination cap. If the cap must be placed where the possibility of

cascading water exists, it is the responsibility of the builder to direct the water away

from the termination cap by using gutters or other means.

Take care to carefully follow the installation instructions for the termination, including

the use of silicon caulking where required.

Figure 35

Figure 34 -

INSTALLING SQUARE HORIZONTAL TERMINATION (SV4.5HT-2)

Siding

Stucco

1-1/4” Maximum Recess of

Square Termination

into Exterior Finishing Material

Exterior Surface of

Framing

Exterior Surface of Siding

Maximum Extent of

Vent Run Sections

Relative to Exterior

Surface of Framing

Interior Surface of

Finished Wall

Last Vent Section.

Use Telescopic Vent

Section (SV4.5LA), If

Necessary

Adapter

SV4.5RCH

Use silicone caulking to seal

the top and sides of the

termination, up to the

underlayment, stucco, or

masonry wall surface.

Caulk

Caulk

Maximum Wall Thickness

10 in. (254 mm)

6 in. to 9-1/4 in.

(152 to 235 mm)

10¹⁄₂"

(267mm)

7"

(178)

5¹⁄₈"

(130 mm)

12¹⁄₈"

(308 mm)

Note: Centerline of Vent Piping is

NOT the Same as the Centerline of

the Framed Opening.

6 to 48 inch Vent Section,

Telescopic vent section,

Elbow or Appliance Collar

Base of Appliance

3"

(76 mm)

1"

(25.4 mm)

Adapter

SV4.5RCH

To help minimize water infiltration it is

recommended that the Firestop/Spacer

(SV4.5HF) be installed on the exterior

side of the wall.

Venting Connection and Exterior Wall Recessing of the Horizontal Square

Termination (SV4.5HT-2).

v

For thicknesses greater than

9-1/4", see Table 8 on Page 22

Maximum wall thickness

9-1/4 in. (235mm)

v