Warning – Superior MILLIVOLT SDVST-N-B User Manual

Page 22

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

22

WARNING

Under no circumstances, may separate sections of

concentric flexible vent pipe be joined together.

See Table 8 as an aid in venting component selection for a particular

range of exterior wall thicknesses.

H = 28 in. (711 mm)

Maximum

7 in. (711 mm)

21 in. (533 mm)

Maximum

u

Wall Firestop / Spacer

(SV4.5HF)

Figure 36

- Side Vent, NO ELBOWS

u

When using Secure Flex, use Firestop / Spacer SF4.5HF

Square termination

(SV4.5HT-2) shown.

H

V

v

Wall Firestop/

Spacer (SV4.5HF)

u

When using Secure Flex, use Firestop / Spacer SF4.5VF

v

When using Secure Flex, use Firestop / Spacer SF4.5HF

Table E

H Maximum

V Minimum

feet

(meter)

feet

(meter)

3

(0.914)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

V + H = 40 feet (12.2 m) Max.

H = 20 ft. (6.096 m) Max.

Example: If 20 feet of (H)

horizontal vent run is needed,

then 4 feet minimum of (V)

vertical vent will be required.

This table shows a 1(V) to

5(H) ratio. For every 1 foot

of vertical, you are allowed 5

feet of (H) horizontal run up

to a maximum (H) horizontal

run of 20 feet.

Figure 37

-

Top Vent, ONE 90 DEGREE ELBOW

Square termination (SV4.5HT-2) shown

Notes:

• Secure Vent™ components (rigid vent pipe and terminal) are shown

in the Figures; Secure Flex™ components (flexible vent pipe and

terminal) may also be used.

Two 45 degree elbows may be used in place of one 90 degree elbow.

The same rise to run ratios, as shown in the venting Figures for 90

elbows, must be followed if 45 degree elbows are used.

SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must

be used anytime vent pipe passes through a combustible floor or ceil-

ing. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer

must be used anytime vent pipe passes through a combustible wall.

• It is very important that the horizontal/inclined run be maintained

in a straight (no dips) and recommended to be in a slightly elevated

plane, in a direction away from the fireplace of 1/4" rise per foot (20

mm per meter) which is ideal, though rise per foot run ratios that are

smaller are acceptable all the way down to at or near level.

The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run

of 20 feet except for installations where an elbow is the only vertical

vent section in the system (see Figure 37).

• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT

WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE

SYSTEM. See Figure 37.

HORIZONTAL VENT FIGURES/TABLES

Square termination

(SV4.5HT-2) shown.

Note:

See Table 8 as an aid in venting component selection for a particular

range of exterior wall thicknesses.

Venting Components Required for Various Exterior Wall Thick-

nesses, when using Square Termination Kit (SV4.5HT-2)

Vent Components Required Exterior Wall Thickness - inches (mm)
Termination Kit Only

6 to 9-1/4 (152 to 235)

Termination Kit and 6 In. Vent

Section (SV4.5L6)

10-3/4 to 14 (273 to 356)

Termination Kit and 12 in.

Vent Section (SV4.5L12)

16-3/4 to 20 (426 to 508)

Termination Kit and Tele-

scopic Section (SV4.5L12)

11-3/4 to 20 (299 to 508)

Table 8

Note: See Figure 35 on Page 21 showing wall thickness

range when using SV4.5HT-2 termination kit only.

Advertising
This manual is related to the following products: