Warning – Superior MILLIVOLT SDVST-N-B User Manual

Page 18

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

18

H

V

V1

V

H

Figure 29

- Side Vent - ONE 90 DEGREE ELBOW

Figure 30

- Top Vent - TWO 90 DEGREE ELBOWS

u

Ceiling Firestop /

Spacer (SV4.5VF)

v

Wall Firestop/

Spacer (SV4.5HF)

u

Ceiling Firestop / Spacer (SV4.5VF)

u

When using Secure Flex, use

Firestop / Spacer SF4.5VF.

v

When using Secure Flex, use

Firestop / Spacer SF4.5HF.

Example: If 20 feet of (H) hori-

zontal vent run is needed, then 4

feet minimum of (V) vertical vent

will be required.

This table shows a 1(V) to 5(H)

ratio. For every 1 foot of (V) verti-

cal, you are allowed 5 feet of (H)

horizontal run, up to a maximum

horizontal run of 20 feet.

An elbow is acceptable as 1 foot

of vertical rise except where

an elbow is the only vertical

component in the system. See

Figure 37.

Table B

H Maximum

V Minimum

feet

(meter)

feet

(meter)

5

(1.524)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

V + V

1

+ H = 40 feet (12.2 m) Max.

H = 20 feet (6.096 meters) Max.

Table A

H Maximum

V Minimum

feet

(meter)

feet

(meter)

2

(0.610)

1

(0.305)

4

(1.219)

2

(0.610)

6

(1.829)

3

(0.914)

8

(2.438)

4

(1.219)

V + H = 40 feet (12.2 meters) Max.

H = 8 feet (2.4 meters) Max.

Ratio V to H ratio is 1:2

u

When using Secure Flex, use Firestop /

Spacer SF4.5VF.

Example: If 8 feet of (H) horizontal vent run is needed, then 4 feet minimum (V) vertical vent will be

required.
This table shows a 1(V) to 2(H) ratio. For every 1 foot of (V) vertical, you are allowed 2 feet of (H)

horizontal run, up to a maximum horizontal run of 8 feet.

VERTICAL VENT FIGURES/TABLES

Notes:

• Secure Vent™ (rigid vent pipe) is shown

in the Figures; Secure Flex™ (flexible vent

pipe) may also be used.

• It is very important that the horizontal/in-

clined run be maintained in a straight (no

dips) and recommended to be in a slightly

elevated plane, in a direction away from

the fireplace of 1/4" rise per foot (20 mm

per meter) which is ideal, though rise per

foot run ratios that are smaller are acceptable

all the way down to at or near level.

SV4.5VF (Secure Vent), SF4.5VF (Secure

Flex) firestop/spacer must be used anytime

vent pipe passes through a combustible

floor or ceiling. SV4.5HF (Secure Vent),

SF4.5HF (Secure Flex) firestop/spacer must

be used anytime vent pipe passes through

a combustible wall.

Two 45 degree elbows may be used in place

of one 90 degree elbow. The same rise to

run ratios, as shown in the venting Figures

for 90 elbows, must be followed if 45 degree

elbows are used.

• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF

VERTICAL RISE EXCEPT WHERE AN ELBOW

IS THE ONLY VERTICAL COMPONENT IN

THE SYSTEM (See Figure 37).

WARNING

Under no circumstances, may sepa-

rate sections of concentric flexible

vent pipe be joined together.

Figure 28

- Top Vent - STRAIGHT

A Vent Restrictor, as

shown in Figure 16,

Page 13, must be used

in this application

u

Ceiling Firestop /

Spacer (SV4.5VF)

u

When using Secure Flex, use Firestop / Spacer

SF4.5VF

40 feet

(12.2 meters)

Maximum