Speed Queen Drying Tumblers SCB50EG User Manual
Page 37
35
M412616
ELECTRICAL REQUIREMENTS
For 30 Pound (13 kg) Narrow Cabinet Tumblers
REQUIREMENTS
Heat Source
Electrical Specs
Wires Required and Terminal Block Connection
Gas
230-50-1
L1
L2
Ground to PE Busbar
Electric
230-50-1
L1
L2
Ground to PE Busbar
Electric
230-50-3
L1
L2
L3
Ground to PE Busbar
Electric
380-50-3
L1
L2
L3
Ground to PE Busbar
Electric
415-50-3
L1
L2
L3
Ground to PE Busbar
Figure 4
GAS DRYING TUMBLERS
Figure 5
GAS DRYING TUMBLERS
240V, 1 Phase, 50 Hz.
120V, 1 Phase, 30 Hz.
Minimum Wire Size
14 AWG (2.081 mm²)
14 AWG (2.081 mm²)
Circuit Breaker
15 AMP
15 AMP
No. of Poles
2
2
ELECTRIC DRYING TUMBLERS
Figure 6
ELECTRIC DRYING TUMBLERS
240V 50 Hz. 1 Ph
240V 50 Hz. 3 Ph
380V 50 Hz. 3 Ph
415V 50 Hz. 3 Ph
Amp Rating
91 Amp
55 Amp
34 Amp
31 Amp
Circuit Breaker
100 Amp
60 Amp
40 Amp
35 Amp
Poles
2
3
3
3
Minimum Wire Size
2 AWG (33.63 mm²) 6 AWG (13.32 mm²) 8 AWG (8.366 mm²) 8 AWG (8.366 mm²)
GROUNDING INSTRUCTIONS
Drying tumbler must be grounded. In event of malfunction or breakdown, grounding will reduce risk of electric
shock by providing a path of least resistance for electric current. Drying tumbler must be connected to a
grounded metal, permanent wiring system; or an equipment grounding conductor must be run with circuit
conductors and connected to PE Busbar.
ࡽ
WARNING
To reduce the risk of fire and electric shock, check with a qualified serviceman for
proper grounding procedures. Improper connection of the equipment grounding
conductor can result in a risk of electric shock.
WARNING
ࡽ
To reduce the risk of fire and electric shock, if electrical supply is coming from a
three phase service, DO NOT connect a “Stinger Leg” to a single phase machine.