ELECTRICAL REQUIREMENTS
For 30 Pound (13 kg) Narrow Cabinet Tumblers

REQUIREMENTS

Heat Source

Electrical Specs

Wires Required and Terminal Block Connection

Gas

230-50-1

L1

L2

Ground to PE Busbar

Electric

230-50-1

L1

L2

Ground to PE Busbar

Electric

230-50-3

L1

L2

L3

Ground to PE Busbar

Electric

380-50-3

L1

L2

L3

Ground to PE Busbar

Electric

415-50-3

L1

L2

L3

Ground to PE Busbar

Figure 4

GAS DRYING TUMBLERS

Figure 5

GAS DRYING TUMBLERS

240V, 1 Phase, 50 Hz.

120V, 1 Phase, 30 Hz.

Minimum Wire Size

14 AWG (2.081 mm²)

14 AWG (2.081 mm²)

Circuit Breaker

15 AMP

15 AMP

No. of Poles

2

2

ELECTRIC DRYING TUMBLERS

Figure 6

ELECTRIC DRYING TUMBLERS

240V 50 Hz. 1 Ph

240V 50 Hz. 3 Ph

380V 50 Hz. 3 Ph

415V 50 Hz. 3 Ph

Amp Rating

91 Amp

55 Amp

34 Amp

31 Amp

Circuit Breaker

100 Amp

60 Amp

40 Amp

35 Amp

Poles

2

3

3

3

Minimum Wire Size

2 AWG (33.63 mm²) 6 AWG (13.32 mm²) 8 AWG (8.366 mm²) 8 AWG (8.366 mm²)

GROUNDING INSTRUCTIONS

Drying tumbler must be grounded. In event of malfunction or breakdown, grounding will reduce risk of electric
shock by providing a path of least resistance for electric current. Drying tumbler must be connected to a
grounded metal, permanent wiring system; or an equipment grounding conductor must be run with circuit
conductors and connected to PE Busbar.

WARNING

To reduce the risk of fire and electric shock, check with a qualified serviceman for
proper grounding procedures. Improper connection of the equipment grounding
conductor can result in a risk of electric shock.

WARNING

To reduce the risk of fire and electric shock, if electrical supply is coming from a
three phase service, DO NOT connect a “Stinger Leg” to a single phase machine.