Series five plc, Enter or change the plc type, Enter or change the memory location – Socket Mobile GFK0121E User Manual

Page 57

Advertising
background image

6

6-4

GFK-0121E

Hand-held Monitor User’s Guide – June 1994

Series Five PLC

For a Series Five PLC, the Hand-held Monitor can
read data from register memory. That includes I/O
data mapped into register memory, (it is easier to
display I/O data with the HHM’s Monitor Block or
Monitor Control Reference function).

For a Series Five PLC, the Device Memory screen
looks like this example:

D E V I C E M E M O R Y 7

M E M : (location)

t g l c h n g e n t r S B A

The top line shows the currently-selected Device
Number (7 in the example above). If there is a
currently-selected memory location, it appears on
the second line of the display as two numbers
separated by a colon.

The number on the left will be:

133

for a Series Five PLC

The number on the right is the actual memory
location that will be read.

From this screen, use the Hand-held Monitor
function keys to:

A. Select a different device on the bus (press F4

(SBA)).

B. Select another memory type (press F2 (chng)).

See right for instructions.

C. Select another reference location in the dis-

played memory type (press F2(chng)). See
right for instructions.

D. Display the current memory contents of the

specified location (press F3 (entr)).

Enter or Change the PLC Type

To enter or change the PLC type:

1. Press F3 (chng). A cursor appears at the left of

the colon. For a Series Six PLC, enter the num-
ber 32768.

2. Press the F3 (entr) key.

Enter or Change the Memory Location

To enter or change the memory location:

1. On the same screen, press F1 ( > ) to move the

cursor to the right of the colon.

2. Press F2 (chng).

3. Enter the byte offset of the data. This is equal

to (2 x register #) – 2. For example, for regis-
ter#100, you would enter (2 x 100) – 2, which
is 198.

I/O Data

Series Five I/O data can be displayed using the
integer result of this formula:

(point number) / 8 + table offset

The table offsets for Series Five I/O are:

channel 1 inputs

32768

channel 2 inputs

32896

channel 1 outputs

33024

channel 2 outputs

33152

Example:

to display channel 2 output 12, you

would enter:12/8 + 33152, which is 33153:

M E M : 1 3 3 : 3 3 1 5 3

Press F3 (ENTR) to save the memory location. To
display the memory content of this location, press
F3 (ENTR) again.

Advertising