Electrical – Kodak RP 50 2J0686 User Manual

Page 126

Advertising
background image

Specifications

B-4

October 2002

Electrical

The KODAK PROFESSIONAL RP 50 LED Printer and Processor are
manufactured to operate within one of the following sets of power constraints or
can be configured to do so by your Kodak representative:

*

Phase selection must be completed at the factory or by a trained Kodak

representative.

*

*

Outside the U.S. and Canada, amperage for the printer is 16A, and the

amperage for the processor is 32A.

NOTE: To prevent processor failures caused by power fluctuations, purchase a

Square-D Buck and Boost Transformer (Model #500SV43F) EK Catalog
#869-7799. Other transformers may not provide satisfactory results.

Consult with your electrical contractor or utility company to ensure that on-site
wiring complies with the printer specifications and that wall outlets use isolated
grounds and comply with codes. Further information is provided in the following
sections.

If the equipment is to be permanently connected, then the equipment must be
provided with its own circuit breaker that is located near the equipment within
easy reach of the operator and marked as the disconnecting device for the
equipment.

A protective earth ground must be supplied when installing the processor.

The unit is an Insulation Category Type II machine, and operates in a Pollution
Degree 2 environment in accordance with IEC 664 (Normal Office Environment).

For technical support, service, repair and fuse replacement information, contact
Eastman Kodak Company’s Technical Assistance Center at 1-800-822-1414.

Nominal Voltage/Frequency

Voltage Range

Power

Consumption

Printer: 200 - 240V, 15A, 50/60
Hz, 1 phase
Processor: 230V, 30A, 50/60
Hz, 1phase or 3 phase
(selectable at installation)

*

Printer: 190 - 254V, 47 -
63 Hz, 1phase, 15 A
(Automatic Sensing)
Processor: 208 - 254V,
47 - 63 Hz, 1phase,
30A

**

Less than
9.12kVA