Operation – Lincoln Electric COMMANDER 500 IM644-A User Manual

Page 22

Advertising
background image

WELDER CONTROLS

(Items 9 through 14 )

9. OUTPUT SELECTOR SWITCH & OUTPUT

CONTROL

These two controls allow you to select between various
welding output slopes and adjust the desired welding
output. Refer to Table B.1 for a description of how
these two controls work.

Table B.1 Output Range Switch and Output Control

Functions

1

If the SELECTOR switch is positioned between settings the previ-
ous setting is maintained until the switch is properly positioned on
a setting.

2

CONTROL also controls O.C.V. while in the 5 sloped output ranges.

10. DIGITAL OUTPUT METERS

The digital output meters are located in the center of
the control panel between the two large control knobs.
The meters allow the output current level to be set prior
to welding in stick mode, and voltage level to be set
prior to welding in the wire modes. During the welding
process the meters display the actual output current
and voltage, within ±5% accuracy.

11. WELDING TERMINALS SWITCH

The toggle switch on the control panel labeled

Welding Terminals Always On

and

Welding

Terminals Remotely Controlled

: is used to control the

operation of the

solid state contactor

which allows for

the selection of

Hot

or

Cold

welding terminals.

B-5

OPERATION

B-5

With the switch in the

Welding Terminals Always On

position the contactor is closed and the welding termi-
nals are always

Hot

.

With the switch in the

Welding Terminals Remotely

Controlled

position the contactor operation is con-

trolled by an Amptrol, Arc Start Switch or some other
type of triggering device through the use of a control
cable connected to the 14-pin MS connector.

When the triggering device is pressed the contactor is
closed and the welding terminals are

Hot

.

When the triggering device is released the contactor is
opened and the welding terminals are

Cold

.

12. LOCAL /REMOTE SWITCH

The toggle switch on the control panel labeled

Local/Remote

gives the operator the option of con-

trolling the output at the welder control panel or at a
remote station.

For remote control the toggle switch is set in the

Remote

position.

For control at the welder control panel, the toggle
switch is set in the

Local

position.

13. 6 - PIN CONNECTOR

The 6-pin connector located on the control panel
allows for connection of interfacing equipment.

14. WELD OUTPUT TERMINALS + AND -

These 1/2 - 13 studs with flange nuts provide welding
connection points for the electrode and work cables.
For positive polarity welding the electrode cable con-
nects to the

+

terminal and the work cable connects

to this

-

terminal. For negative polarity welding the

work cable connects to the

+

terminal and the elec-

trode cable connects to this

-

terminal.

AUXILIARY POWER CONTROLS

(Items 15 - 19 )

15. 120/240VAC RECEPTACLE

This is a 120/240VAC (14-50R) receptacle that pro-
vides 240VAC or can be split for 120VAC single phase
auxiliary power. This receptacle has a 50 amp rating.
Refer to the AUXILIARY POWER RECEPTACLES sec-
tion in the installation chapter for further information
about this receptacle. Also refer to the AUXILIARY
POWER OPERATION section later in this chapter.

16. 50 AMP CIRCUIT BREAKERS

These circuit breakers provide separate overload cur-
rent protection for each 120V circuit at the 240V recep-
tacle.

COMMANDER 500

Sloped Output for
Pipe Welding.

Touch Start TIG
Welding

Constant Current
Output for
Fabrication and
General Purpose
Welding

Constant Voltage
Output for MIG
Wire or CORED
WIRE Welding

5 Range

Settings

90, 150, 250,

350, 500 (Max.

current on each

setting)

1 Range setting

15-200 Amps

1 Range setting

30-575 Amps

1 Range setting

12 to 48 Volts

Provides a fine

adjustment of

welding current

from

Min (1) to Max

(10) within each

range

Provides Fine

Voltage

Adjustment

Selector

Switch

1

Application

Control

2

Advertising