B-10

OPERATION

B-10

COMMANDER 500

Welding

Output Range

Setting

30-575

500
350
250
150

90

Welding Output

500A/40V
500A/40V
350A/30V
250A/29V
150A/27V

90A/25V

Permissible

Power - Watts

(Unity Power

Factor)

0
0

9500

12000
12000
12000

Permissible

Current in

@120 V ±10% *

0
0

80*

100**
100**
100**

Auxiliary
Amperes

@ 240 V ±10%

0
0

40
50
50
50

* Each duplex receptacle is limited to 20 amps.
** Not to exceed 50 A per 120 VAC branch circuit when splitting the 240

VAC output.

TABLE B.4 Commander 500 Simultaneous Welding and Power

Loads

TABLE B.5 Commander 500 Extension Cord Length

Recommendations

Current

(Amps)

15
15
20
20
25
30
38
50

Voltage

(Volts)

120
240
120
240
240
240
240
240

Load

(Watts)

1800
3600
2400
4800
6000
7200
9000

12000

30
60

(9)

(18)

40
75
30
60

(12)
(23)

(9)

(18)

75

150

50

100

90
75

(23)
(46)
(15)
(30)
(27)
(23)

125
225

88

175
150
120
100

(38)
(69)
(27)
(53)
(46)
(37)
(30)

175
350
138
275
225
175
150
125

(53)

(107)

(42)
(84)
(69)
(53)
(46)
(38)

300
600
225
450
250
300
250
200

(91)

(183)

(69)

(137)

(76)
(91)
(76)
(61)

Maximum Allowable Cord Length in ft. (m) for Conductor Size

Conductor size is based on manimum 2.0% voltage drop.

14 AWG

12 AWG

10 AWG

8 AWG

6 AWG

4 AWG