Monitoring system, Rack monitoring system, Nstallation and commissioning – Lindy Carbon Monoxide Alarm User Manual

Page 13

Advertising
background image

I

NSTALLATION AND COMMISSIONING

I

NSTALLATION AND COMMISSIONING

3

13

Monitoring System

Rack Monitoring System

3.3.1

3.3

ELECTRICAL INSTALLATION

Connections and cabling

Connection

Cabling

Mains montoring

Digital Out

1

Fuse plug > 3.3.3

2

Mains Connections > 3.3.2

3

MAINS MONITORING

Mains monitoring connections

4

DIGITAL OUT

Digital switching outputs 1 - 4

5

DIGITAL IN

Digital inputs 1 - 8

6

ALERT IN

Alarm inputs 1 - 4

7

TEMPERATURE/HUMIDITY

• Before connecting the RMS to the mains, properly connect all the

components to the rear of the device. Observe VDE regulations!

• Only have mains voltages connected by authorised skilled persons.

• Use wire end ferrules when connecting litz cables!

• Observe the information on documentation (> A2)!

• Avoid tensile loads, serious kinking and damage to the cables as a

result of sharp edges or unsuitable tools (optional cable protection avai-

lable).

– 3 terminal pairs L1, L2 and L3 for the connection of 3 mains voltages

– Potential-free, no common earth reference

– UIN 50 … 255 V AC
– Only have mains voltages connected by authorised skilled persons.

Observe VDE regulations!

- 4 terminal pairs for the connection of 4 consumers

– Potential-free relay switch contacts

– Relay 108 cycles purely mechanically, 105 cycles at maximum loads-

witched

– Maximum load switched 1.5 A at 230 V AC, 2 A at 30 V DC

temperature or humidty sensor
connections 1-4

8

UPS IN

UPS connections 1 - 2

9

10 BASE T

RJ45 Ethernet network connection

10

AUX

Serial interface for the control
and monitoring of external devices

11

COM

Serial interface for terminal connection

1

2

3

4 5 6 7 8 9 10 11

1

2

3

4 6 8 9 10

RMS LITE

RMS ADVANCED