51

Monitoring System

Rack Monitoring System

Objects under
digitalInTable
(1.3.6.1.4.1.1909.10.2.1)

for example:
number of changes of input 9:
1.3.6.1.4.1.1909.10.2.1.1.5.9

Objects under
alertInTable
(1.3.6.1.4.1.1909.10.2.2)

for example :
Reset sensors on Alert In 2
1.3.6.1.4.1.1909.10.2.2.1.3.2 := 1

Object under ups I

N

T

ABLE

(1.3.6.1.4.1.1909.10.2.3)

Variable Type

Value

Access

1 digitalInEntry

1 digitalInIndex

INT RO

2 digitalInDescr

DS RW

3 digitalInState

INT

{ off (1), on (2)} RO

4 digitalInLastChange

TT RO

5 digitalInChanges

CNT RO

Variable

Type

Value

Access

1 alertInEntry

1 alertInIndex

INT

RO

2 alertInDescr

DS

RW

3 alertInState

INT

{off (1), on (2)} RO

4 alertInLastChange

TT

RO

5 alertInChanges

CNT

RO

6 alertInReset

INT

{default (1)

RW

alertIn-reset (2)}

Variable Type

Value

Access

1 upsInEntry

1 upsInIndex

INT

RO

2 upsInDescr

DS

RW

3 upsInState

INT

{off (1), on (2)} RO

4 upsInLastChange

TT

RO

5 upsInChanges

CNT RO

Advertising