E

XAMPLE CONFIGURATION

E

XAMPLE CONFIGURATION

5

Rack

Preconfigured filters with an
example of terminal assign-
ment.

• Connect sensors to the
suggested terminals.

Example of filter configuration
using filter 1 (temperature).

• Activate the filter by setting the
respective effect to “thru” or
“invert” (preset: “off”).
• Make individual settings (effect,
warnings, …) for each filter
required. See also > 4.9.2.

Examples of filter settings

TEMPERATURE/HUMIDITY input 1
with simple comparison:
Alarm if temperature > 35 °C.
TEMPERATURE/HUMIDITY input 2
with window comparison:
Alarm if temperature < 5 °C or
> 45 °C. See also > 4.9.4.

When the RMS is delivered, the most common applications (descri-
bed in part in the following) have been preconfigured so that com-
missioning involves setting fewer parameters.