Monitoring System

Rack Monitoring System

4.9.4

TEMPERATURE/MAINS/HUMIDITY
INPUTS

The filter inputs for measured
values are displayed with the
threshold, mode and effect.
They have a flexible structure for
the creation of larger/smaller
comparisons or window compari-
sons.

Thus the following filter conditi-
ons can easily be realised:

1)

Simple larger/smaller compari-

son (switch if the input variable is
smaller/larger than the
threshold). Example 1 – Switch if
temperature 1 > 35 °C: mode A
“>”; threshold A 35; mode B
“off”; threshold B any value;
effect “thru”.

2)

“Window comparison” (switch

if the input variable is inside/outsi-
de a defined range) Example 2 –
Switch if voltage 1 is between
210 V and 240 V: Mode A “>”;
threshold A 210; Mode B “<”;
threshold B 240; effect "thru"
Example 3 – Switch if humidity 1
is less than 30 % or greater than
80 %: Mode A “>”; threshold A
30; Mode B “<”; threshold B 80;
effect “invert”

[A] M

ODE

-A [B] M

ODE

-B

Set comparison module..

[1] T

HRES

-A [2] T

HRES

-B

Set threshold.

[E] E

FFECT

State how the input acts on
the OR element.
thru switched

through

off switched

off

invert switched

through

in

inverted fashion

[-] P

REVIOUS

I

NPUT

Selection pointer to previous input.

[+] N

EXT

I

NPUT

Selection pointer to next input.

[?] H

ELP

Explanation of the menu items.

[Q] Q

UIT

Jump back to the previous menu..