Mechanical Considerations

8

4.0

M

ECHANICAL

C

ONSIDERATIONS

4.1

Determining Placement in the Conditioned Space

Liebert XDVs should be placed above or on top of the cabinets that generate the greatest amount of

heat. If heat loads are dispersed evenly throughout the room, the Liebert XDV modules may be

spread out accordingly.
The Liebert XDV is engineered to fit atop computer enclosure cabinets. Figure 8, below, illustrates

the unit’s dimensions and the location of pipes, the fan tray and power connections. (An optional kit is

available to permit suspending the Liebert XDV from either Unistruts or from the overhead struc-

ture; see 5.2 - Suspended Mounting Method.).

Figure 8

Liebert XDV dimensions

Table 2

Dimensional data

Illustration

Key

Dimension

Measurement,

in (mm)

DT

Depth Top

39-1/2 (1003)

DB

Depth Bottom

29-5/8 (752)

W

Width

22-7/8 (581)

H

Height

14 (356)

PH

Piping Height,

hard-piped

18-5/8 (473)

Piping Height,

one-shot option

19-5/8 (498)

DF

Depth Front

9-7/8 (250)

DT

DF

PH

H

DB

W

DPN000770
Page 2, Rev. 6

Liebert XDV With

Pre-charged Option

(all dimensions except piping

height are the same as for the

hard-piped setup, see Table 2)

Liebert XDV With Hard-piped Arrangement