The Liebert XDV’s fan controls are on the front of the unit, near the fans, for easy access. Each switch

controls the operation of one fan (see Figure 36). The separate switches permit the use of only one

fan at a time, reducing the airflow if the Liebert XDV’s full cooling capacity is not needed.
The Liebert XDV’s primary and secondary circuit breakers are also on the front of the unit. They are

at the top left when facing the Liebert XDV (see Figure 36).

Figure 36 Fan switches

9.1

Start the Liebert XDV

The Liebert XDV fans must be on before starting the Liebert XDP or Liebert XDC that will supply

coolant to the Liebert XDVs.
To start the Liebert XDV, press either of the rocker switches to turn on one or both of the Liebert

XDV’s fans.

NOTE
One of the Liebert XDV’s fans must be turned on before either the Liebert XDP or Liebert XDC

is switched on.
One of the Liebert XDV’s fans must be operating at all times that the Liebert XDP or Liebert

XDC is operating. Operating either the Liebert XDP or the Liebert XDC without at least one of

the Liebert XDV’s fans rotating may cause a system malfunction.

On/Off Switch
for Left Fan

Primary and Secondary
Circuit Breakers

On/Off Switch
for Right Fan