2 changing the air intake location, Changing the air intake location, Figure 9 – Liebert Cooling System XDV User Manual

Page 15: Changing the liebert xdv’s air intake location, Warning

Advertising
background image

Mechanical Considerations

9

4.2

Changing the Air Intake Location

The Liebert XDV comes from the factory with the air intake on the rear of the unit. If required for

your application, this can be changed so that the Liebert XDV takes in heated air from the bottom.

This is done more easily and safely before the unit is mounted on a computer cabinet.

To change the air intake:
1. Loosen the six screws holding the grille on the rear of the Liebert XDV (see Figure 9).
2. Remove the grille and lay it aside for use later.
3. Remove the channel bracket holding the two solid metal plates to the bottom of the Liebert XDV.

It is secured with two screws, one on either end.

4. Lift the two solid plates out of the bottom of the Liebert XDV.
5. Optional—replace the channel bracket, securing it with the two screws removed in Step 3.
6. Lay the perforated grille down with the screws pointing up
7. Lay the two solid plates on the grille with the screws through the matching holes of the plates.
8. Hold the grille and plates together and attach the assembly to the rear of the Liebert XDV with

the screws.

Figure 9

Changing the Liebert XDV’s air intake location

!

WARNING

Risk of high-speed moving parts. Can cause death, injury and equipment damage.
Before opening the Liebert XDV, shut the unit off and disconnect all electrical power. Wait for

the Liebert XDV’s fans to stop rotating before beginning to open the unit.

Remove rear inlet grille, taking care not to loosen
the screws. Remove screws and channel bracket
from base of unit, remove solid plates. Using the
screws from the rear grille, reinstall the solid
plates on the exterior rear of the unit.
Place rear grille in a secure area for future use.

Solid
plates

Grille