Piping

24

6.6

Connection Methods—One-Shot Connections

The assembly and connection means used for piping in the Liebert XD system are the same as those

used in conventional refrigeration systems. Observe all standard practices during installation and

startup to prevent damage and contamination.
Both supply and return fittings may be supplied with optional, one-shot connections. These fittings

contain pressurized R-134a refrigerant inside the Liebert XDV.

If the unit includes the optional, factory-installed, one-shot style connections, proceed with 6.7 - Field

Installation of Liebert Flex Pipe Kit on Liebert XDV and see Figure 26.
If the unit does not include flex piping, refer to 6.4.1 - Holding Charge—Hard-Piped Units.

Figure 26 Piping location and connection sizes—pre-charged units with one-shot connections

Table 4

Branch piping sizes for refrigerant loop

Pipe Function

Size / Equivalent Pipe Length

Liebert XDP/Liebert XDC supply line, from

Liebert XDP/Liebert XDC supply

to farthest Liebert XDV

1-1/8" OD (1.025" ID) for lengths up to 60 feet (18m)
1-3/8" OD (1.265" ID) for lengths over 60 but less than 175 feet (18 to 53m)

Liebert XDP/Liebert XDC return line, from

farthest Liebert XDV

to Liebert XDP/Liebert XDC return

2-1/8" OD (1.985" ID) for lengths up to 60 feet (18m)
2-5/8" OD (2.465" ID) for lengths over 60 but less than 175 feet (18 to 53m)

From Liebert XDV supply to supply line of

Liebert XDP/Liebert XDC

1/2" OD (0.430" ID) for lengths up to 6 feet (1.8m)
5/8" OD (0.545" ID) for lengths over 6 feet but less than 35 feet (1.8-10.6m)

From Liebert XDV return to return line of

Liebert XDP/Liebert XDC

5/8" OD (0.545" ID) for lengths up to 6 feet (1.8m)
7/8" OD (0.785" ID) for lengths over 6 feet but less than 35 feet (1.8-10.6m)

!

CAUTION

Risk of sudden refrigerant discharge. Can cause injury and loss of charge.
If the optional pre-charged option is chosen, the Liebert XDV unit is shipped with a full

charge of R-134a refrigerant under pressure. Do not remove the pipe caps or plugs before the

unit is ready for connection to Liebert XD Piping.
Supply and return fittings on the pre-charged Liebert XDV units are one-shot connections. Do

not disconnect one-shot connections after they have been connected. Disconnection will

release pressurized R-134a refrigerant from the Liebert XDV.

Detail
Area “A”

Detail “A”

Return
Connection
5/8"

Supply
Connection
1/2"

Top View