6.10 Disconnecting a Liebert XDV With Liebert Flex Pipe From a Liebert XD System

NOTICE

Before uninstalling a Liebert XDV with Liebert Flex Pipe from the prefabricated piping

mains: With the fans running, close the supply service valve, wait approximately

two minutes, then close the return service valve.
Removing a Liebert XDV from above a cabinet will require two people. Read all instructions

before beginning.

Tools Required

• Two adjustable wrenches, maximum adjustment size of 2-1/2 inches
• Two ladders
• Phillips head #2 screwdriver
• Lift mechanism, if the Liebert XDV is suspended above cabinet

1. Ensure the Liebert XDV fan switches are both On and the fans are operational.
2. Close the service valve in the supply line to the Liebert XDV (smaller coupler).
3. With the Liebert XDV fans running, wait two minutes.
4. Close the service valve in the return line to the Liebert XDV (larger coupler).
5. Turn the fan power switches to the Off position. Once the fan switches are turned Off, unplug the

power cords from their power source.

6. Locate and have at the ready the caps and plugs for both ends of the supply and return couplers.
7. Loosen the female supply coupler from the male supply coupler (smaller coupler). This requires

two adjustable wrenches. Refer to Figure 29.

8. The Liebert XDV side of the female coupler must be held stationary while the collar on the

coupler is being loosened. Refer to Figure 29.

9. Disconnect the coupler.

Figure 31 Profile view of the Liebert XD system with one-shot connections

10. Place the protective dust cap and plug back onto both ends of the coupler on the Liebert XDV and

the port pipe.

!

CAUTION

Risk of sudden discharge of pressurized refrigerant. Can cause equipment damage or injury.
Do not disconnect threaded refrigerant couplers at the unit cabinet end without relieving

system pressure. Reclaim any refrigerant during removal of unit from system.

Liquid Sensing
(optional)
Disconnect wiring
prior to moving XDV

Primary and
Secondary
IEC Power
Cord

Rear of the XDV

Serial Tag

Fan Power
Switches

One-Shot Connections

One-Shot Support Bracket

Service
Valve

Return
Line

Supply
Line