POWERWARE 9 BATTERY BACKUP TIMES (in minutes)

700-1000 VA Models
Load

Standard

(VA/Watts)

Internal Batteries

+1 EBM

+2 EBMs

200/140

37

271

546

400/280

19

142

278

700/490

9

72

156

850/595

6

59

124

1000/700

5

48

104

1250-2000 VA Models

Load

Standard

(VA/Watts)

Internal Batteries

+1 EBM

+2 EBMs

+3 EBMs

+4 EBMs

400/280

46

177

331

501

682

700/490

25

96

180

272

370

850/595

21

76

142

214

292

1000/700

16

61

115

174

237

1250/875

11

46

87

131

179

1500/1050

8

37

70

106

144

1800/1260

6

30

57

85

116

2000/1400

5

26

49

74

100

2500-3000 VA Models

Load

Standard

(VA/Watts)

Internal Batteries

+1 EBM

+2 EBMs

+3 EBMs

+4 EBMs

1250/875

16

57

90

150

200

1500/1050

13

55

72

120

160

2500/1750

7

28

48

68

88

3000/2100

5

25

38

54

70

Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

POWERWARE 9 EBC BACKUP TIMES (in minutes)



Discharge Time

EXTERNAL EBC-48 CABINETS. For use with 1250, 1500, 2000 VA
VA

Watts

+1 EBC-48

+2 EBC-48s

+3 EBC-48s

650

455

838

800

560

662

1000

700

506

1200

840

406

1250

875

387

1400

980

340

761

1500

1050

315

705

1600

1120

294

658

1800

1260

258

578

2000

1400

224

501

802

EXTERNAL EBC-72 CABINETS. For use with 2500, 3000 VA
VA

Watts

+1 EBC-72

+2 EBC-72s

+3 EBC-72s

+4 EBC-72s

1000

700

387

1500

1050

245

2000

1400

175

368

2500

1750

135

284

446

3000

2100

107

225

354

490

1. Actual runtimes not supported by Powerware LanSafe software. *Discharge time @100% of the UPS rating.
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

SINGLE-PHASE SERIES 9
Powerware 9125 (700–3000 VA) EBM Backup Times